State diagram
State transition of M+SF_MODSEL_R
i_bActivate=OFF
0
i_bS_SetMode
S_SetMode
=OFF
Error
1
C100H
i_bS_SetMode=ON AND
(R_TRIG at
i_bS_SetMode =OFF)
AND i_bS_Unlock=ON
i_bS_ModeX changed
AND i_bS_Unlock=ON
i_bS_ModeX
changed
i_bS_Unlock
=OFF
2
Note 1: Error 1: More than one i_bS_ModeX=ON is selected at the same time.
Error 2: The i_bS_ModeX=OFF state remains for longer than i_dModeMonitorTime.
Note 2: The transition from any state to the Idle state due to i_bActivate=OFF is not shown. However these transitions have the highest priority (0).
4 SAFETY FB SPECIFICATIONS
56
4.9 M+SF_MODSEL_R
Idle
0000H
1
i_bActivate=ON
i_dModeMonitorTime<0 OR
i_dModeMonitorTime>60000
0=<i_dModeMonitorTime=<60000
AND R_TRIG at i_bReset=ON
1
4
3
Mode
2
Changed
8005H
5
R_TRIG=ON
at i_bReset
(i_bAutoSetMode=ON OR
R_TRIG at
i_bS_SetMode=ON)
AND i_bS_Unlock=ON
AND (one i_bS_ModeX=ON)
2
Error 1
Mode
Selected
1
8000H
3
i_bS_Unlock=ON
3
Mode
Locked
1
8004H
Parameter
Error
C005H
1
Error 2
Error
R_TRIG at
Open
i_bReset=ON
-Circuit
2
C002H
Error 1
2
i_bReset=OFF
Error
Short
-Circuit
1
C001H
i_bReset=ON
AND
R_TRIG at i_bReset=OFF
Error 1 AND i_bS_Unlock=ON
o_bReady=OFF
o_bReady=ON
i_bReset=OFF
1
Reset
Error 2
1
C004H
i_bReset=ON
AND
R_TRIG at i_bReset=OFF
Reset
1
Error 1
C003H
o_bS_ModelXSel=OFF
o_bS_AnyModeSel=OFF
o_bS_ModelXSel=ON
o_bS_AnyModeSel=ON