9.11 PI CONTROL PARAMETERS (CONTROL PANEL: MENU PAR -> P12)
Code
Parameter
P12.1 PI activation
P12.2 PI controller gain 0.0
PI controller I-
P12.3
time
Keypad PI refer-
P12.4
ence
P12.5 Setpoint source
P12.6 Feedback source 0
Feedback mini-
P12.7
mum
Feedback maxi-
P12.8
mum
Error value inver-
P12.9
sion
Table 9.11: PI control parameters
NOTE! These parameters are shown, when P13.1 = 0.
Parameters
Min
Max
Unit
0
2
1000
%
0.00
320.0 s
0.0
100.0 %
0
3
2
0.0
100.0 %
0.0
100.0 %
0
1
Default
ID
0 = Not used
0
163
1 = PI for motor control
2 = PI for external use
100.0
118
10.00
119
0.0
167
0 = Keypad PI reference,
P12.4
1 = Fieldbus
0
332
2 = AI1 Only in API FULL
& LIMITED
3 = AI2 Only in API FULL
0= Fieldbus
1 = AI1 Only in API FULL
2
334
& LIMITED
2 = AI2 Only in API FULL
0.0
336
0 = No minimum scaling
100,0 = No maximum scal-
100.0
337
ing
0=No inversion (Feed-
back<Setpoint->Increase
0
340
PI Output)
1=Inverted (Feedback<Set-
point->Decrease PI Output)
Honeywell
Note
62-0312—02