Honeywell
Terminal
1
+10Vre
2
AI1
3
GND
6
24Vout
7
GND
8
DI1
9
DI2
10
DI3
A
A
B
B
24
RO 21
25
RO 22
Table 7.3 : General purpose application default I/O
configuration and connections for API LIMITED version
P) = Programmable function, parameter lists and descriptions, chapters 9 and 10.
Terminal
3
GND
6
24Vout
7
GND
8
DI1
A
A
B
B
24
RO 21
25
RO 22
Table 7.4 : General purpose application default I/O
configuration and connections for API RS-485 version
P) = Programmable function, parameter lists and descriptions, chapters 9 and 10.
62-0312—02
API
API LIMITED
Signal
Factory preset
Ref. voltage out
Analog signal in 1
Freq. reference
I/O signal ground
24V output for DI's
I/O signal ground
Digital input 1
Start forward
Digital input 2
Start reverse
Digital input 3
Preset speed B0
RS485 signal A
FB Communication
RS485 signal B
FB Communication
Relay out 2
ACTIVE (Relay
opened) = FAULT
API RS-485
Signal
Factory preset
I/O signal ground
24V output for DI's
I/O signal ground
Digital input 1
1 = Start forward
RS485 signal A
FB Communication
RS485 signal B
FB Communication
Relay out 2
ACTIVE (Relay
opened) = FAULT
Description
Maximum load 10 mA
P)
0 - +10 V Ri = 200 k
±
20
%, max. load 50
mA
P)
0 - +30 V Ri = 12 k min
P)
P)
Max. switching load:
250Vac/2A or 250Vdc/
P)
0.4A
Description
±
20
%, max. load 50
mA
0 - +30 V Ri = 12 k min
Max. switching load:
250Vac/2A or 250Vdc/
P)
0.4A
7
32
Ω
Ω
Ω