Perform test run without motor. Perform either Test A or Test B:
A) Control from the I/O terminals:
7
B) Control from the keypad:
Run the no-load tests without the motor being connected to the process,
if possible. If this is not possible, secure the safety of each test prior to
running it. Inform your co-workers of the tests.
8
Connect the motor to the process (if the no-load test was run without the
motor being connected)
9
62-0312—02
Commissioning
• Turn the Start/Stop switch to ON position.
• Change the frequency reference (potentiometer)
• Check in the Monitoring Menu that the value of Output frequency
changes according to the change of frequency reference.
• Turn the Start/Stop switch to OFF position
• Select the keypad as the control place with par. 2.1. You can also
move to keypad control by pressing the navigation wheel for 5
seconds.
• Push the Start button on the keypad
• Check in the Monitoring Menu that the value of Output frequency
changes according to the change of frequency reference
• Push the Stop button on the keypad
• Switch off the supply voltage and wait up until the drive has
stopped.
• Connect the motor cable to the motor and to the motor cable ter-
minals of the frequency converter.
• See to that all Start/Stop switches are in Stop positions.
• Switch the mains ON
• Repeat test 7A or 7B
• Before running the tests, make sure that this can be done safely.
• Inform your co-workers of the tests.
• Repeat test 7A or 7B.