Honeywell SmartVFD COMPACT User Manual page 68

Hvfdcd1b0003 series; hvfdcd1b0005 series; hvfdcd1b0007 series; hvfdcd1b0010 series; hvfdcd1b0015 series; hvfdcd1b0020 series; hvfdcd1b0030 series; hvfdcd3c0005 series; hvfdcd3c0007 series; hvfdcd3c0010 series; hvfdcd3c0015 series; hvfdcd3c0020
Hide thumbs Also See for SmartVFD COMPACT:
Table of Contents

Advertisement

Honeywell
If tripping is selected the drive will stop and activate the fault stage. Deactivat-
ing the protection, i.e. setting parameter to 0, will reset the thermal model of
the motor to 0%.
9.8
M
OTOR AMBIENT TEMPERATURE
When the motor ambient temperature must be taken into consideration, it is
recommended to set a value for this parameter. The value can be set between
-4 °F (-20 °C) and 212 °F (100 °C).
9.9
M
OTOR COOLING FACTOR AT ZERO SPEED
The cooling power can be set between 0-150.0% x cooling power at nominal
frequency. See Figure 10.8.
9.10
M
OTOR THERMAL TIME CONSTANT
This time can be set between 1 and 200 minutes.
This is the thermal time constant of the motor. The bigger the motor, the bigger
the time constant. The time constant is the time within which the calculated
thermal model has reached 63% of its final value.
The motor thermal time is specific to the motor design and it varies between
different motor manufacturers.
If the motor's t6-time (t6 is the time in seconds the motor can safely operate at
six times the rated current) is known (given by the motor manufacturer) the
time constant parameter can be set basing on it. As a rule of thumb, the motor
thermal time constant in minutes equals to 2xt6. If the drive is in stop state the
time constant is internally increased to three times the set parameter value.
See also Figure 10.9.
62-0312—02
Parameter Descriptions
P
cooling
100%
par.9.9=40%
0
Figure 10.8: Motor cooling power
Overload area
I
T
f
f
n
66
10

Advertisement

Table of Contents
loading

Table of Contents