Pi Control Parameters (Control Panel: Menu Par -> P12) - Honeywell SmartDrive Compact User Manual

Table of Contents

Advertisement

Honeywell
8.11 PI CONTROL PARAMETERS (CONTROL PANEL: MENU PAR -> P12)
Code
Parameter
P12.1 PI activation
P12.2 PI controller gain
PI controller
P12.3
I-time
Keypad PI
P12.4
reference
P12.5 Setpoint source
P12.6 Feedback source
Feedback
P12.7
minimum
Feedback
P12.8
maximum
Error value
P12.9
inversion
Table 8.11: PI control parameters
NOTE! These parameters are shown, when P13.1 = 0.
Parameters
Min
Max
Unit Default
0
2
0,0
1000
%
100,0
0,00
320,0
s
10,00
0,0
100,0
%
0
3
0
2
0,0
100,0
%
0,0
100,0
%
100,0
0
1
ID
0 = Not used
0
163
1 = PI for motor control
2 = PI for external use
118
119
0,0
167
0 = Keypad PI reference,
P12.4
0
332
1 = Fieldbus
2 = AI1
3 = AI2
0 = Fieldbus
2
334
1 = AI1
2 = AI2
0,0
336 0 = No minimum scaling
100,0 = No maximum
337
scaling
0 = No inversion (Feed-
back<Setpoint->Increase
PI Output)
0
340
1 = Inverted
(Feedback<Setpoint-
>Decrease PI Output)
43
Note
8

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents