Electrical installation
5.7

Correction of supply current

Attention in case of continous load:
Due to the capacitive input impedance of
DC-Bus, the input current is deformated.
This guides to RMS -values higher than the sinus-based calculated values. Fuses,
contactors and line filters have to be selected in respect to this effect.
In typical servo application with Stop/Go-operation (S3-Operation), the
rating to nominal data will be sufficient.
In other cases, the value has to be corrected using the following diagram.
Correction-Factor
637+/KD6R02..10.S4-7
637+/KD6R16..30.S3-7
637+/KD6R02..10.S3-3
Example:
Drive type 637+/KD6R16.S4-3 is supplied by AC 230V 3-ph.
Output data to the motor: AC 200V 16A
Output-power: Pout = 200V x 16A x 1,73 = 5,54 kW
This output-power must be generated by:
calculated supply-current Iac sinus =5,54kW / (230V x 1,73) = 13,9 A
Correction-Factor from diagram: 1,6
RMS. Supply-Current Ieff = Iac sinus x 1,6 = 22,3 A
Result :
All supply-equipment has to be selected in respect tothe enhanced current.