Fuses, Contactors, Filters - Eurotherm 637+/D6R KD6R Product Manual

Digital servodrive the 4-th generation
Table of Contents

Advertisement

5.6

Fuses, contactors, filters

Compact units
Fuses, Contactors
4)
RCD-switch
mains input currents
mains protection
1)
protector-switch
2)
mains fuse
2)
Line filters
4)
generall
industrial env.
max. motor cable 50m
(EN55011 A)
residential env.
max. motor cable 20m
(EN55011 B)
industrial env.
max. motor cable 50m
(EN55011 A)
residential env.
max motor cable 20m
(EN55011 B)
industrial env.
max. motor cable 20m
(EN55011 A)
residential env.
max motor cable 20m
3)
(EN55011 B)
Plug-in modules
Fuses, contactors,
filters
generall
fuses
peak making currents
filters
filter models
1) recommended for UL-requirements: Bussmann Type FRS-R, 600V, use only UL-approved fuse-holders !
2) recommended, Klöckner Moeller for instance
3) Measurement of conducted emissions only
4) for applications with continuous load: see notes in chapter 5.7
637+/ KD6R 02
KD6R 04
.S4
.S4
-3
-7
-3
not recommended. Required setpoint: 300 mA, no protection against life danger
[A]
3,5
model
T10A
T10A
model PKZM0-16
PKZM0-16
model
DIL 00M
DIL 00M
only for use in earth referenced supplies(TN). Current drain to PE !
model
LNF E 1*230/012
up to AC 230V !!
+
ferrite core FR 3
model
LNF E 1*230/012
up to AC 230V !!
+
ferrite core FR 3
model
LNF B 3*480/008
+
ferrite core FR 3
model
LNF B 3*480/008
+
ferrite core FR 3
3-phasen, max. 3 Geräte versorgt durch einen gemeinsamen Filter
model
LNF B 3*480/018; LNF B *480/033 + ferrite core FR
(according to ref.measurements with 3 units, supplied by common line)
model
LNF B 3*480/018; LNF B 3*480/033 + ferrite core FR
(according to ref.measurements with 3 units, supplied by common line)
637+ / D6R 02
D6R 04
.S4
.S4
-3
-7
-3
4)
1)
Orientation: Table for compact units and the addition of rated currents of used
units on the DC-Bus. Depending on the application, energy sharing effects by
DC-link may reduce the required supply current considerable.
Rule of the thumb: single-phase operation: 2...3 times of added rated currents
Rule of the thumb: 3-phase operation: 1,5...2 times of added rated currents
Depending on power-supply unit, limiting equipment is requiered (delay contactor)
only for use in earth referenced supplies(TN). Current drain to PE !
Orientation: Table of compact units. Further models: see separate manual
Product-manual Model: 637+/D6R KD6R
KD6R 06
KD6R 10
.S4
.S4
-7
-3
-7
-3
-7
5
7,5
12
T10A
T20A
PKZM0-16
PKZM0-16
DIL 00M
DIL 00M
single-phase
3-phase
LNF B 3*480/018
ferrite core FR 6
LNF B 3*480/018
ferrite core FR 3
other models upon request
other models upon request
D6R 06
D6R 10
.S4
.S4
-7
-3
-7
-3
-7
07-02-09-01-E-V0402.doc
KD6R 16
KD6R 22
.S4
.S4
-7
-7
19
26
T25A
(T32A) 35A (T32A) 35A
PKZM0-25 PKZ2/ZM32 PKZ2/ZM32
DIL 0M
DIL 0M
not possible
not possible
LNF B 3*480/033
+
ferrite core FR 6
LNF B 3*480/033
+
ferrite core FR 3
D6R 16
D6R 22
.S4
.S4
-3
-7
-3
-7
-3
KD6R 30
.S4
-7
30
DIL 0M
+
+
D6R 30
.S4
-7
49