Wiring according to EMC (structure of a CE-typical drive
system)

Basic rules

The structure of a CE-typical drive system will be more efficient by means of wiring according to
EMC. Wiring according to EMC is determined by the type of installation and the care taken.
Figure 2 shows two important rules for installation:
careful structure
good shielding
good earthing
separated cable routing
0
1
2
3
4
5
6
7
L < 500 mm
Installation principle according to EMC
Mounting plate with electrically conductive surface
Control cable to function module, connect the shielding to the EMC shield sheet (PES) with a surface as large as
possible
2-pole terminal for motor PE and motor shield
PE of the motor cable
Shield of the motor cable
Shielded low-capacitance motor cable
≤ 75 pF/m; from 2.5 mm
2
(Core/core 1.5 mm
Shielded PTC cable or thermal contact cable
Connect the cable shields to the EMC shield sheet (PES) with a large surface. Use the enclosed shield clamps.
Star or delta connection as indicated on the motor nameplate
EMC cable gland (not included in the scope of supply)
Wirin g accord ing to EM C
Always observe these basic rules
8200 vector 3 ... 11 kW
PES
PE
PE
PE
M
3~
8
9
L < 40 mm
PES
PES
8200vec066
≤ 100 pF/m; core/shield ≤ 150 pF/m)
2
EDBEMV82EV EN 3.0
0
1
2
3
4
5
6
7
L < 500 mm
PES
PES
9