Lenze 8200 vector series Manual page 21

Global drive frequency inverters 0.25 kw ... 11 kw
Hide thumbs Also See for 8200 vector series:
Table of Contents

Advertisement

Show/Hide Bookmarks
Fig. 6
3.2.2.2
l
Wiring of the motor filter 400 V
Install the motor filter so that the cable length does not exceed 200 m:
– This cable does not have to be shielded.
The cable from the motor filter to the motor is subject to the same rules as for the motor
cable.
Note!
The connections +UG and -UG of the motor filter must be directly connected with
the connections +UG and -UG of the controller (no fuses in the connecting cable)!
Otherwise the motor filter can be destroyed.
3/PE AC 400/500 V
+UG
-UG
+UG
8200 vector
E82ZMxxx34B
U V W
U V W
Wiring of the motor filter 400 V
Limitation of harmonic currents
For complying with the limit values according to EN 61000-3-2 the following measures must be taken
for the 8200 vector frequency inverters. Please observe that the radio interference suppression
measures already mentioned must be taken in addition.
Essential measures for complying with the limit values according to EN 61000-3-2
8200 vector
Type
Mains voltage
[V]
E82EV551K4Cxxx
3/PE
3/PE
AC 400 V
E82EV751K4Cxxx
C000
8200 vector with integrated RFI filter
C200
8200 vector without integrated RFI filter
+ N
Mains choke is required in addition
Assignment table of mains chokes
8200 vector
Type
Mains voltage
[V]
E82EV551K4Cxxx
3/PE
3/PE
AC 400 V
E82EV751K4Cxxx
Wiring according to EMC
-UG
U1 V1 W1
M
3~
Power
[kW]
0.55
0.75
Power
[kW]
0.55
0.75
EDBEMV82EV EN 3.0
Power connections
Measure
Measure
C000 + N
C000 + N
C200 + N
Mains choke
Order No.
E82ZN3A1500H003
E82ZN3A1500H003
19