Lenze 8200 vector series Manual page 19

Global drive frequency inverters 0.25 kw ... 11 kw
Hide thumbs Also See for 8200 vector series:
Table of Contents

Advertisement

Show/Hide Bookmarks
3.2.1.2
l
Limitation of harmonic currents
For complying with the limit values according to EN 61000-3-2 the following measures must be taken
for the 8200 vector frequency inverters. Please observe that the radio interference suppression
measures already mentioned must be taken in addition.
Essential measures for complying with the limit values according to EN 61000-3-2
8200 vector
Type
Mains voltage
[V]
E82EV251K2Cxxx
E82EV371K2Cxxx
1/N/PE
1/N/PE
AC 230 V
E82EV551K2Cxxx
E82EV751K2Cxxx
E82EV551K2Cxxx
3/PE
3/PE
AC 230 V
E82EV751K2Cxxx
C000
8200 vector with integrated RFI filter
C200
8200 vector without integrated RFI filter
+ N
Mains choke is required in addition
+ AF
Active filter is required in addition (on demand)
Assignment table of mains chokes and active filters
8200 vector
Type
Mains voltage
[V]
E82EV251K2Cxxx
E82EV371K2Cxxx
1/N/PE
1/N/PE
AC 230 V
E82EV551K2Cxxx
E82EV751K2Cxxx
E82EV551K2Cxxx
3/PE
3/PE
AC 230 V
E82EV751K2Cxxx
Wiring according to EMC
Power
[kW]
0.25
0.37
0.55
0.75
0.55
0.75
Mains choke
Power
Order No.
[kW]
0.25
ELN1-0900H005
ELN1 0900H005
0.37
0.55
0.75
0.55
E82ZL75132B
E82ZL75132B
0.75
EDBEMV82EV EN 3.0
Power connections
Measure
Measure
C000 + N
C000 + N
C200 + N
C000 + AF
C000 + AF
C200 + AF
C000 + N
C000 + N
C200 + N
Active filter
Active filter
on request
on request
17

Advertisement

Table of Contents
loading

Table of Contents