Ambient Conditions - Vega VEGAWELL 52 Operating Instructions Manual

Submersible pressure transmitter with ceramic measuring cell 4...20 ma
Hide thumbs Also See for VEGAWELL 52:
Table of Contents

Advertisement

Ʋ F
: Deviation
Kl

Ambient conditions

Ambient temperature
Ʋ Suspension cable PE
Ʋ Suspension cable PUR, FEP
Storage and transport temperature
Process conditions
Max. process pressure, transmitter
Ʋ Measuring range 0.1 bar (1.45 psig)
Ʋ Measuring range 0.2 bar (2.9 psig)
Ʋ Measuring ranges from 0.4 bar
(5.8 psig)
Pressure stage, process fitting
Ʋ Screw connection for suspension
cable
Ʋ Thread on the housing
Product temperature, depending on the version
Suspension cable
PE
PUR
FEP
Vibration resistance
Shock resistance, version G1
Electromechanical data
Suspension cable
Ʋ Configuration
Ʋ Wire cross-section
Ʋ Wire resistance
Ʋ Tensile strength
Ʋ Max. length
Limited by the overload capability max. pressure of the measuring cell.
5)
Limited by the overload capability max. pressure of the measuring cell.
6)
Limitation by cable entry
7)
Tested according to the guidelines of German Lloyd, GL directive 2.
8)
VEGAWELL 52 • 4 ... 20 mA
-40 ... +60 °C (-40 ... +140 °F)
-40 ... +80 °C (-40 ... +176 °F)
-40 ... +80 °C (-40 ... +176 °F)
15 bar (218 psig)
20 bar (290 psig)
30 bar (435 psig)
316L: PN 3, PVDF: unpressurized
PN 3
Transmitter
All versions
All versions
PE coating
All versions
PE coating
mechanical vibrations with 4 g and 5 ... 100 Hz
50 g, 2,3 ms according to EN 60068-2-27 (mechanical
shock)
six wires, one suspension wire, one breather capillary,
screen braiding, foil, mantle
0.5 mm²
≤ 0.036 Ω/m
≥ 1200 N (270 pound force)
1000 m (3280 ft)
5)
6)
7)
Product temperature
-20 ... +60 °C (-4 ... +140 °F)
-20 ... +80 °C (-4 ... +176 °F)
-20 ... +60 °C (-4 ... +140 °F)
-20 ... +80 °C (-4 ... +176 °F)
-20 ... +60 °C (-4 ... +140 °F)
8 Supplement
8)
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents