Mastervolt Mass Combi 12/2000-100 Quick Installation page 4

120v inverter and battery charger

Advertisement

Quick installation
DIP switch settings.
10
See chapter 6 of the user's manual for detailed description of the DIP switch settings.
Recommended DIP-switch settings:
Dip Switch Bank A:
Single Inverter System: SW1 - OFF, SW2 – OFF.
Output frequency 60Hz: SW3 – OFF.
High power mode (energy saving modes disabled): SW4 – OFF, SW-5 – OFF. The Economy mode (SW4 – ON,
SW-5 – ON) will save some power but allows clocks and such to run.
Battery type. Standard Lead acid: SW6 – OFF, SW7 – OFF; Gel or AGM: SW6 – ON, SW7 – OFF.
Ground relay: SW8- ON. During inverter operation of the Mass Combi, the Neutral wire (N) of the inverter output
will be internally connected to the Ground (PE / GND)
Dip Switch Bank B:
Power Sharing function, set to maximum power is SW1- OFF, SW2- OFF, SW3 ON. If the Remote APC or
Masterlink MICC is used, you should adjust the Mass Combi to this setting. Then the maximum input power can
be adjusted by means of these remote control panels.
If Power support is used (boosting power with inverter on Short break output), SW4- ON. If this is used, SW5
must be OFF.
If Generator and Main power boosting is selected, SW-5- ON. Please note this mode is not recognized by ABYC
as two power sources are mixed. If this mode is still going to be used, SW4- must be OFF.
Power Quality. Normal setting is SW6- OFF. This allows unit to operate on power from 45-65 Hz. SW6- ON
opens this frequency window to 35- 65 Hz for poorly synchronized generators.
For operation with remote panels, with the main switch on the Mass Combi to ON.
SW7- OFF: the remote On-Off switch turns off or on both the charger and inverter remotely.
SW7- ON: the remote On-Off switch only turns off or on the inverter section only. Battery charger always
operates when external AC power is available.
SW8- OFF. Equalize should only be used with lead acid batteries at the end of their life cycle and only when
careful monitoring of battery conditions can be observed. See also chapter 6 of the user's manual.
11
Check all wiring.
If the wiring is OK:
Tighten the cable glands;
Close the connection
compartment;
Place the DC fuse (when
placing this fuse, a spark can
occur!);
Switch on the DC source;
Switch on the AC source.
Mastervolt International B.V,
P.O.Box 22947, NL-1100 DK Amsterdam, The Netherlands.
Mass Combi 120V
SW1 SW2 Setting
SW3 Setting
SW4 SW5 Setting
OFF
OFF
60 Hz
OFF
P0 single
OFF
OFF
ON
50 Hz
ON
OFF
ON
OFF
P1 mode
OFF
ON
OFF
ON
P2 mode
ON
ON
ON
ON
P3 mode
Parallel mode
Inverter Freq.
Energy mode
Mass Combi Settings Menu
SW5
SW1 SW2 SW3
Setting
SW4
Setting
OFF
OFF
OFF
OFF
OFF
30 AMPS
Disabled
ON
OFF OFF
ON
ON
25 AMPS
Enabled
OFF
ON
OFF
15 AMPS
ON
ON
OFF
10 AMPS
*
*
ON
Power
Generator
50 AMPS
support
mains supp.
Power sharing
Tel.: +31-20-3422100
SW6 SW7 Setting
SW8 Setting
OFF
High power
OFF
Standard
OFF
Disabled
OFF
ON
Idle 40VA
ON
GEL - AGM
Enabled
OFF
ON
Idle 150VA
Traction
ON
ON
Econ. 109V
Forced float
Battery type
Ground relay
SW7
Setting
SW6
Setting
Setting
SW8
High
OFF
OFF
Equalize
Disabled
Combi
Mode
ON
Low
ON
Enabled
Inverter
Starts
With
On-Off
Pulse
Power
Combi /
quality
Inv. control
Equalize
12
Switch on the Mass Combi.
The LED-indicators will blink
several times
After a few seconds the Mass
Combi starts operating.
If not, immediately switch off the DC power supply
and AC power supply. Investigate the cause of the
malfunctioning. See Trouble shooting chapter of the
user's manual.
Email: info@mastervolt.com
English
DIP switch bank A.
DIP switch bank B.
Web: www.mastervolt.com v1.0 080731US