2-5-5 Wiring for Manual Reset (Interlock is Valid)

(Wiring Example of the Control Category 4)
This is the general configuration using one set of the emitter and receiver facing each other.
The control output (OSSD 1 / 2) turns OFF if the light is blocked.
<In case of using I/O circuit for PNP output with SF4B-□C>
Gray cable
Gray cable
with black line
Interlock function
External device monitor function Valid
Auxiliary output
The device output is selected depending on the connecting state of the output polarity setting wire
(shield). Incorrect wiring may cause the lockout state.
* Symbols
Switch S1
Vs to Vs - 2.5V (sink current 5mA or less): Emission halt (Note 1), Open: Emission
K1, K2: External device (Forced guided relay or magnetic contactor)
Notes: 1) Vs is the applying supply voltage.
2) For resetting, refer to "3-2 Interlock Function."
© Panasonic Industrial Devices SUNX Co., Ltd. 2014
Ramco National
(Brown) +V
(Pale purple) Interlock setting input
(Pink) Emission halt input / Reset input
(Yellow-green / Black) Auxiliary output
(Shield) Output polarity setting wire
(Blue) 0V
(Orange) Synchronization +
(Orange / Black) Synchronization -
(Orange / Black) Synchronization -
(Orange) Synchronization +
(Yellow-green) External device monitor input
(Brown) +V
(Black) Control output 1 (OSSD 1)
(White) Control output 2 (OSSD 2)
(Shield) Output polarity setting wire
(Blue) 0V
Valid (Manual reset)
Can be used
800-280-6933 | nsales@ramcoi.com
*S1
+
Load
-
K1
K2
K1
K2
www.panasonicsensors.com
Wiring
24V DC
±10%
49