Installation Of Indoor Unit - Gree GVA24AL-K3NNC7A/I Service Manual

Refrigerant:r410a
Table of Contents

Advertisement

Model
24/48/55K

8.5 Installation of Indoor Unit

Step one: choosing installation Iocation
Recommend the installation location to the client and then
confirm it with the client.
Step two: open piping hole
1.Choose the position of piping hole according to the direction
of outlet pipe.
2.Open a piping hole with the diameter of Φ70mm on the
selected outlet pipe position. In order to drain smoothly, slant
the piping hole on the wall slightly downward to the outdoor
side with the gradient of 5-10°. (As show in Fig.1)
Indoor
Outdoor
Fig.1
°
5-10
Note:
1.Pay attention to dust prevention and take relevant
safety measures when opening the
hole.
2.The plastic expansion particles are not provided and
should be bought locally.
Step three: outlet pipe
1. The pipe can be led out in the direction of left, right or rear.
(As show in Fig.2)
2. After confirming the direction of outlet pipe, loosen the
screws at the upper and lower adjusting baffle to let the
connection pipe/drain pipe connects the indoor unit. (As show
in Fig.3)
left
left
upper and lower adjusting baffle
Step four: connect the pipe of indoor unit
1. Take out the left and right screw cover and then remove
the screws on air-inlet panel to remove the panel.(As show in
Fig.4)
2. Aim the pipe joint at the corresponding bellmouth.(As show
in Fig.5)
36
Capacity of air switch
25A
Model
Piping hole
All models
Φ70mm
Φ70mm
Fig.2
right
back
right
back
Fig.3
3. Pretightening the union nut with hand.
4. Adjust the torque force by referring to the following sheet.
Place the open-end wrench on the pipe joint and place the
torque wrench on the union nut. Tighten the union nut with
torque wrench.(As show in Fig.6)
5. Wrap the indoor pipe and joint of connection pipe with
insulating pipe, and then wrap it with tape. (As show in Fig.7)
screw
air-inlet
panel
Fig.4
open-end wrench
union nut
pipe
torque wrench
indoor pipe
Fig.6
Refer to the following table for wrench moment of force:
Hex nut diameter(mm)
Φ6
Φ9.52
Φ12
Φ16
Φ19
Step five: install drain hose
1. Connect the drain hose to the outlet pipe of indoor unit.(As
show in Fig.8)
2. Bind the joint with tape.(As show in Fig.8)
3. Add insulating pipe in the indoor drain hose in order to
prevent condensation.(As show in Fig.10)
drain hose
outlet pipe
Fig.8
drain hose
insulating pipe
Fig.10
Step six: connect wire of indoor unit
1. Make the power connection wire go through the cable-
cross hole of indoor unit(As show in Fig.11)
Service Manual
pipe
pipe joint
union nut
Fig.5
insulating pipe
Fig.7
.
Tightening torque(N . m)
15~20
30~40
45~55
60~65
70~75
drain hose
outlet pipe
tape
Fig.9
Installation and Maintenance