LEDs and connectors
2.2 LEDs
DIAG
NETWORK
(red / green)
(red / green)
Connection to communications partners
green
green
flashing
green
flashing
green
flashing
green
flashing
green
Quality of the mobile wireless connection
-
-
-
-
-
-
-
-
-
flashing red
VPN connections
-
-
-
-
Loading firmware
30
CONNECT
SIGNAL
QUALITY
(green)
(yellow /
green)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
VPN
Meaning
(green)
-
Connection established to at least one part-
ner, CPU in RUN
-
Connection established to at least one part-
ner, CPU in STOP
-
No partner reachable, CPU in RUN
-
No partner reachable, CPU in STOP
-
Telecontrol configuration exists, partner not
reachable, CPU in RUN mode
-
Telecontrol configuration exists, partner not
reachable, CPU in STOP mode
-
Good network (-73 ... ≥ -51 dBm)
-
Medium strength network (-89 ... -74 dBm)
-
Weak network (-109 ... -90 dBm)
-
No network (≤ -110 dBm)
-
Missing external power supply
VPN connection established
No VPN connection established
No VPN connection configured on the CP
Loading firmware.
The "DIAG" LED flashes alternating red and
green.