Locating BACnet Interface PCB
Bacnet Port and Interface Dip Switch Setting
DS2 switches at OFF position
(factory set-up)
Pull up disable
120 Ohm termination
(last node) disable
Pull down disable
DS2 switches at ON position
Pull up enable
120 Ohm termination
(last node) enable
Pull down enable
(Illus. 22)
TJ1
DS2
DS2
DS2
SKE-XL BACnet Steam Humidifier
Installation Instructions and User Manual

BACnet Interface Set-up

The BACnet interface PCB is located on the top right
corner inside the electrical compartment.
BACnet interface PCB.
O
1 2 3 4 5 6
O
1 2 3 4 5 6
N
N
JP2
BACnet Port
(2 wires twisted pair)
A +
B -
TB1
(Illus. 23)
DS1-1 : Mode selection
OFF = Mode Operational
ON = Mode Configuration
DS1-2&3 : Baud rate selection
Baud rate
Switch #2
9600
19200
38400
76800
(factory set-up)
20
Not used
Baud rate selection
Mode selection
(factory set-up)
Switch #3
OFF
OFF
ON
OFF
OFF
ON
ON
ON