Water supply installation should conform to local codes and regulations.
Any installation work must be carried out by suitably qualified personnel.
Water inlet
Neptronic® SKG3 Humidifier is designed to be used with mains, reverse osmosis,
Specifications
deionised and de-mineralized water.
Maximum water supply pressure: 10 to 70psig (70 to 480kPa)
Minimum water temperature: 49˚F (+4˚C)
Maximum water temperature: 104˚F (+40˚C)
Water supply line
To facilitate servicing, a shut off valve (not supplied) should be installed in the water
Installation
line, within 40'' (1m) of the humidifier.
SKG3
Stage 4 – Water Supply Installation
Model
SKG3-
110 to 810
Gasket
2 ¾'' (70)
Water Inlet connection
dimensions in bracket are in mm
Water inlet
Connection size
Feed Water supply line
¼ turn Shut off Valve
Gasket
Flexible Hose
(Fig. 23)
17
SKG3 Steam Humidifier
1/2'' NPT
Male