Programming Mode - Neptronic SKE90 Installation Instructions Manual

Electric steam humidifier ske series ske-xl bacnet
Hide thumbs Also See for SKE90:
Table of Contents

Advertisement

To enter into programming mode, please push
programming step in the menu push the same button twice.
Unless other instructions, you can make a selection by using
Seq
Display
#
CONTROL
01
EXTERNAL
SP SOURC
01A
INTERNAL
SETPOINT
01B
40% RH
DUCT SRC
01C
DISABLE
DUCT SP
01D
80% RH
DRAIN
02
8 HRS
RUNNING
03
0645HRS
SERVICE
04
1000HRS
LOCK ON
05
80% PWR
RESET
06
ALRM NO
CTRL INP
07
2-10 VDC
button at any time, to advance the program function to the next
Description
Selection of Control mode.
If External is selected, the control demand will be
received by the control input; if Com Port is selected,
the control demand will be received by the
communication port (BACnet option).
Selection of the Set Point Source (Control Internal
only).
Selection of source for room humidity set point.
Selection of room relative humidity set point.
(SP Source Internal only)
Hi limit control mode.
Selection of the source for the duct high limit relative
humidity (Control Internal only).
Selection of high limit relative humidity set point.
(Duct Source External only).
Setting of automatic drain cycle of evaporation
chamber.
Note: In general, harder the water is, more often the
drain cycle must be. Drain cycle setting does not affect
the AFEC system.
reading and reset
Number of running hours
To reset this counter: After service has been done,
press simultaneously the
seconds to reset the number of hours of operation to
zero.
The timer reset stops the CHECK indicator from
flashing.
Hour span between services.
Note: In general, harder the water is, lower the number
of hours of operation before service must be.
Selection of humidifier capacity reduction.
i.e.: In this case, the humidifier will deliver 80% of its
maximum rated output when at full demand.
Reset of alarm
To reset an alarm, press simultaneously the
buttons.
Control signal input selection.
25
SKE-XL BACnet Steam Humidifier
Installation Instructions and User Manual

Programming Mode

&
buttons on control panel.
and
buttons for 30
and
Values
Internal or External
or Com Port
Default: External
Internal or External
or Com Port
Default: Internal
Percentage
From 10 to 90%
Disable or External
or Com Port
Default: Disable
Percentage
From 10 to 90%
From 1 to 24 hours
Increment: 1 hour
Default: 4 hours.
N/A
From 400 to 1500 hours.
Increment: 100
Default: 1000 hours.
From 00 to 100%.
Increment: 1%
Default: 100%
Yes or No
Default: No
0-10VDC, 2-10VDC,
0-20mA or 4-20mA
Default : 2-10VDC