Brooks MT3809G Metal Tube Supplemental Manual

Brooks MT3809G Metal Tube Supplemental Manual

Variable area flowmeter with foundation fieldbus communications
Hide thumbs Also See for MT3809G Metal Tube:

Advertisement

Installation and Operation Manual
X-DPT-FF-MT3809G-Alarms-eng
Part Number: 541B218AAG
TM
Model MT3809G F
Fieldbus
December, 2017
OUNDATION
®
Supplemental Manual for Brooks
Model MT3809G Metal Tube,
Variable Area Flowmeter with
TM
Foundation
Fieldbus Communications

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MT3809G Metal Tube and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Brooks MT3809G Metal Tube

  • Page 1 Installation and Operation Manual X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION ® Supplemental Manual for Brooks Model MT3809G Metal Tube, Variable Area Flowmeter with Foundation Fieldbus Communications...
  • Page 2 Read before proceeding! Brooks Instrument designs, manufactures and tests its products to meet many national and international standards. These products must be properly installed, operated and maintained to ensure they continue to operate within their normal specifications. The following instructions must be adhered to and integrated into your safety program when installing, operating and maintaining Brooks Instrument products.
  • Page 3 We recommend that you read this manual in its entirety. Should you require any additional information concerning Brooks products and services, please contact your local Brooks Sales and Service Office listed on the back cover of this manual or visit www.BrooksInstrument.com...
  • Page 4 Installation and Operation Manual X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION THIS PAGE WAS INTENTIONALLY LEFT BLANK...
  • Page 5: Table Of Contents

    Contents Installation and Operation Manual X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Paragraph Page Number Number Section 1 Introduction Introduction ........................... 1-1 Section 2 Installation Installation ............................. 2-1 Section 3 F Fieldbus Data OUNDATION Fieldbus Data ......................3-1 OUNDATION Section 4 Getting Started Getting Started ..........................
  • Page 6 Contents Installation and Operation Manual X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION THIS PAGE WAS INTENTIONALLY LEFT BLANK...
  • Page 7: Section 1 Introduction

    OUNDATION 1.1 Introduction This document will provide an overview of FOUNDATION™ Fieldbus software interface for Brooks Instrument Variable Area Flowmeters model MT3809G with FOUNDATION™ Fieldbus transmitter. This document describes the function and transducer blocks along with grids that show the available parameters.
  • Page 8 Section 1 Introduction Installation and Operation Manual X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION THIS PAGE WAS INTENTIONALLY LEFT BLANK...
  • Page 9: Section 2 Installation

    Section 2 Installation Installation and Operation Manual X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION 2.1 Installation Carefully read and follow the instructions for installation and operation given in the Metal Tube Variable Area Flowmeters Installation and Operation Manual X-VA-MT3809G-MT3810G-eng.
  • Page 10 Section 2 Installation Installation and Operation Manual X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION THIS PAGE WAS INTENTIONALLY LEFT BLANK...
  • Page 11: Section 3 F

    Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION 3.1 F Fieldbus Data OUNDATION Hardware Identification Manufacturer Brooks Instrument Model (Device Name) MT38xx Type of Device Metal Tube Variable Area Flowmeter Manufacturer ID 0x000246 Device Type ID 0x2000 Device Revision...
  • Page 12 Section 3 F Fieldbus Data Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION THIS PAGE WAS INTENTIONALLY LEFT BLANK...
  • Page 13: Section 4 Getting Started

    The DD files for the MT38xx FF can be found on website www.fieldbus.org Find the files under <End User Resources>, then <Registered Products>, choose for manufacturer <Brooks Instrument> and for Category <Flow>, then <Search>. From here you can open either SLA Series, or MT38xx, and download the DD files.
  • Page 14 Section 4 Getting Started Installation and Operation Manual X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION THIS PAGE WAS INTENTIONALLY LEFT BLANK...
  • Page 15: Section 5 Transducer Blocks

    The parameter structure of the Analog Input Transducer block is specifically defined for the Brooks Instrument VA Flowmeter. A detailed decription of the block follows in the next section. 5.2 Analog Input Transducer Block The following table lists and describes the parameters of the Analog Input Transducer Block.
  • Page 16 HW_REV Hardware revision of the transmitter Read String represents the version Visible Read/ BROOKS_PASSWORD Password protection for manufacture settings Brooks password *************** string Write Extra message field for indicating the transmitter. This Visible ASCII Read/ MESSAGE Blank...
  • Page 17 Section 5 Transducer Blocks Installation and Operation Manual X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Parameters of the Analog Input Transducer Block (continued) Table 5-1 Initialized Parameter Name Description Valid Values Value ASCII Calibrated Read/ MODEL_NUMBER Model number of the assembled device Max 20 chars Value...
  • Page 18 Section 5 Transducer Blocks Installation and Operation Manual X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Parameters of the Analog Input Transducer Block (continued) Table 5-1 Initialized Parameter Name Description Valid Values Value Read/ PULSE_OUTPUT.UOM Unit of measurement used to generate the pulses Supported UOMS Gallon Write...
  • Page 19 Section 5 Transducer Blocks Installation and Operation Manual X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Parameters of the Analog Input Transducer Block (continued) Table 5-1 Initialized Parameter Name Description Valid Values Value Test interface to test the alarm and pulse outputs. TEST Testing is only possible when in testing mode Read/...
  • Page 20 Section 5 Transducer Blocks Installation and Operation Manual X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION THIS PAGE WAS INTENTIONALLY LEFT BLANK...
  • Page 21: Section 6 F

    Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Fieldbus Guidelines OUNDATION Source: F ™ Fieldbus Application Guide - 31.25 kbit/s Wiring and OUNDATION Installation. Refer to the F ™...
  • Page 22 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Terminator OUNDATION Fieldbus Interface Terminator FD = Field Device Figure 6-3 Fieldbus Network with Chained Devices In Figure 6-2 more field devices have been added to the network of Figure 6-1.
  • Page 23 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION 1st Trunk OUNDATION Fieldbus Repeater Interface 2nd Trunk FD = Field Device Figure 6-4 Adding a Repeater to the Fieldbus Network four devices, one of them being the repeater.
  • Page 24 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Fieldbus Power Supply Wire Pair OUNDATION Signals Fieldbus Interface Terminator Terminator FD = Field Device Figure 6-6 Adding a Power Supply to the Fieldbus Network For new installations, ask cable vendors for "fieldbus cable".
  • Page 25: Fieldbus Interface Setup-Reference

    Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION 6.2 F Fieldbus Interface Setup-Reference OUNDATION Note:This interface setup is showing an example of how a device connection is made to a Softing FG-110 FF linking device using the Softing FF-CONF configuration tool.
  • Page 26 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Step 3: Assign appropriate PD Tag and Node ID as desired. Default Assignment Assignment to be chosen (example) Result of assignment configuration.
  • Page 27 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Step 4: Create New Project for Network Configuration...
  • Page 28 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Step 5: Add FG-110 Linking Device and MT3809G device to Network Configuration Step 6: In Network Configuration, configure HSE device (FG-110 Linking Device) for appropriate Device ID, PD Tag and IP address Configuration FG-110 Linking device:...
  • Page 29 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Default settings of MT3809G H1 device Step 7: Configure MT3809G device for appropriate Device ID, PD Tag and Node ID...
  • Page 30 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Step 8: To operate the AI function block, a link must be created between AI block and IT block. For this purpose, go to Functionblock Application tab.
  • Page 31 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Step 9: Add AI block to Source Functionblock(s) List, and add IT block to Sink Functionblock(s) List 6-11...
  • Page 32 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Step 10: Add AI output to Source pin(s), and IT input to Sink pin(s): 6-12...
  • Page 33 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Step 11: Click connect icon button, choose Project <Save>, choose Download <Download project> , and AI output is now connected to IT input 6-13...
  • Page 34 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Step 12: To operate AI function block, go to AI block in Network Configuration and set following parameters: 6-14...
  • Page 35 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Step 13: First set MODE_BLK.TARGET to OOS (out of service), to be able to set desired OUT_SCALE UOM and OUT_SCALE value of AI function block. 6-15...
  • Page 36 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Step 14: Write desired OUT_SCALE UOM and OUT_SCALE value settings, for example 200 m3/h. 6-16...
  • Page 37 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Step 15: After writing desired OUT_SCALE settings, set MODE_BLOCK.TARGET back to Auto. 6-17...
  • Page 38 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Step 16: OUT.VALUE and PV.VALUE are now indicated as per 200 m3/h FS. (In the example indicated as 44.4, so currently flowing at 22.2% FS). 6-18...
  • Page 39 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Step 17: Alarm settings in AI function block. For this example, only HI_FLOW and HI_HI_FLOW alarms are set. Alarm limit example values (100 and 150) are referenced to 100% OUT.SCALE value (i.e.
  • Page 40 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Step 18: When OUT.VALUE > 100, Hi Alarm is presented 6-20...
  • Page 41 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Step 19: When OUT.VALUE > 150, Hi Hi Alarm (and Hi Alarm) are presented 6-21...
  • Page 42 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Step 20: When OUT.VALUE < 100, Current Alarm is not indicated anymore. 6-22...
  • Page 43 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Step 21: To reset unacknowledged alarms, acknowledge HI_HI_ALARM and HI_ALARM. 6-23...
  • Page 44 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Step 22: Unacknowledged alarms have been reset. 6-24...
  • Page 45 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Step 23: Setting transmitter’s physical alarm output contacts. Go to AI transducer block, and set Hi-Flow and Lo-Flow limits as per desired values (in this example 90 and 10 respectively for a 0 - 100 UOM Primary Value scale).
  • Page 46 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Step 24: Observing flow alarm conditions PV value < 10 • Lo Flow Alarm • Transmitter Contact Output B closed •...
  • Page 47 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION PV value > 90 • Hi Flow Alarm • Transmitter Contact Output A closed • Alarm Status AI transducer block: 8 6-27...
  • Page 48 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION 90 > PV value > 10 • No Flow Alarm • Transmitter Contact Output A and B both open •...
  • Page 49 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Step 25: Switch alarm output contacts to latching type. Note: The latching mode of the flow alarms is only reflecting to the alarm output contacts, and NOT to the Alarm Status in the AI transducer block.
  • Page 50 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG Model MT3809G F Fieldbus December, 2017 OUNDATION Step 26: Alarm output contacts reset. After Alarm Reset, alarm output contacts are switched to open condition. 6-30...
  • Page 51 Section 6 F Fieldbus Guidelines Installation and Operation Manual OUNDATION X-DPT-FF-MT3809G-Alarms-eng Part Number: 541B218AAG December, 2017 Model MT3809G F Fieldbus OUNDATION Step 27: Alarm output contacts disabling. To discontinue alarm output contacts operation, set Hi Flow Alarm and Lo Flow Alarms to disabled. Alarm output contacts remain in open condition, regardless of any PV value.
  • Page 52 BROOKS SERVICE AND SUPPORT Brooks is committed to assuring all of our customers receive the ideal flow solution for their application, along with outstanding service and support to back it up. We operate first class repair facilities located around the world to provide rapid response and support.