E07 Outdoor unit sending failure to indoor unit
1.
Error Detection Method
It is judged an error when a unit itself cannot receive (discrepancy) a signal within a 3-minute period that it had sent.
•
Outdoor main PC board error
•
The setting of the terminal resistor select switch on the outdoor main PC board is set incorrectly.
2.
Error Diagnosis
Is the indoor/outdoor operation line connected to more than one
1 Outdoor
1-1
outdoor unit? (Network wired?)
unit
control
Is the SHORT on the terminal resistor switch on the outdoor main
PC board
1-2
PC board set to one unit, and the others are OPEN?
Is the terminal resistor select switch on the outdoor main PC board
1-3
set to OPEN?
1-4
Is the indoor/outdoor operation line opened or shorted?
1-5
Replace the outdoor unit main PC board.
•
For information on the procedures for replacing the outdoor main PC board, refer to the manual that is packaged with the
service board.
A746894 : (U-60PE1E5, U-71PE1E5)
(for single-phase outdoor unit PCB)
TERMINAL EEPROM
A746845 : (U-125PE1E5, U-140PE1E5)
(for single-phase outdoor unit PCB)
TERMINAL
EEPROM
5-17
A746844 : (U-100PE1E5)
(for single-phase outdoor unit PCB)
TERMINAL
A746968 : (U-71PE1E8)
A746967 : (U-100PE1E8, U-125PE1E8, U-140PE1E8)
(for 3-phase outdoor unit PCB)
TERMINAL
TERMINAL
Yes
1-2
No
1-3
Yes
1-4
Set the SHORT to
No
one unit only
Make the SHORT
Yes
setting
No
1-4
Yes
Correct the wiring
No
1-5
EEPROM
EEPROM
EEPROM
5