Panasonic S-36PU1E5 Technical Data & Service Manual page 187

R410a inverter, indoor/outdoor units, 4-way cassette, ceiling, wall mounted, low shilhouette ducted, ducted
Table of Contents

Advertisement

This equipment complies with EN/IEC 31000-3-12 provided that the short-circuit power Ssc is greater than or equals to
the interface point between the user's supply and the public system. It is the responsibility of the installer or user of the equipment
to ensure; by consultation with the distribution network operator if necessary that the equipment is connected only to supply with a
short-circuit power Ssc greater than or equals to
Ssc
: Short circuit power
SG
: Shows the earth for the shielded cable.
Model name
U-60PE1E5
U-71PE1E5
U-71PE1E8
U-100PE1E5
U-125PE1E5
U-140PE1E5
U-100PE1E8
U-125PE1E8
U-140PE1E8
3 Models U-71PE1E8, U-100PE1E8, U-125PE1E8 and U-140PE1E8 are intended for professional use.
Consult with the supply utility for permission of electrical connection.
Electrical work should be handled by Certificated Electrical work personnel by following "Technical standard of electric installation"
and "Regulated regulations of nation".
Adjust wire size, length, earth leakage breaker, and fuse capacity according to each country's Wiring regulations.
If capacity of power supply circuit and enforcement are not enough, it can causes the electric shock and a fire.
Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conforms to CENELEC (HAR)
NOTE
rating specifications) or use the cables based on IEC standard. (245 IEC57, 245 IEC66)
1 Use a shielded cable for the control cable. Overall extension less than 500m
For the shield part of the shielded cable, twist the end out, crimp it with a
round terminal, and connect it to the SG screw.
After crimping it with a round terminal, wrap it with insulating tape so there
are no spaces and adjust it so the shield part does not touch any live parts.
Be sure that the shield part of the shielded cable does
Caution
not touch the terminal block or any live parts.
Failure to do so may lead to electric shock or fire.
2 kVA.
Maximum electric
Power supply
current
220/230/240V~
220/230/240V~
380/400/415V 3N~
220/230/240V~
220/230/240V~
220/230/240V~
380/400/415V 3N~
380/400/415V 3N~
380/400/415V 3N~
1-181
1
Control cable
18A
0.75mm²
18A
0.75mm²
7A
0.75mm²
25A
0.75mm²
28A
0.75mm²
30A
0.75mm²
9A
0.75mm²
10A
0.75mm²
11A
0.75mm²
Crimp the round terminal
Shield part
2 kVA at
2
Ssc
4050kVA
4050kVA
3
6000kVA
6000kVA
6000kVA
3
3
3
Wrap it well with insulating
tape so there are no spaces.