1
Use a round type terminal with an insulation sleeve for connecting to the terminal block.
Use the appropriate screwdriver for tightening the terminal screws.
Small sized screwdriver damages the head of the screw and
cannot tighten it properly.
There is risk of damaging the screw if the terminal screw is
over tightened. Tighten with the appropriate torque.
Screw diameter name
M4
M5
Direction to pull out wires
Front direction
Seal wiring holes after wiring using included protection
(other holes are for connecting conduit pipe)bush.
Earth lead wire set up
Be sure to connect the wires correctly to terminal board with
connecting the crimp type ring terminal to the wires.
If connecting two separate wires to a single crimped terminal,
place the two crimped terminal wires together as shown in
Fig. A. (If the arrangement shown in Fig. B is used, poor contacts
or contact damage may result.)
OUTDOOR UNIT/3-PHASE MODEL
Power supply (220/230/240V~)
Circuit breaker
Switch
Earth
L
N
SG
U1
U2
R1
R2
Indoor unit
Wired remote
Tightening torque N•m (kgf•m)
1.57 ~ 1.96 (0.16 ~ 0.2)
1.96 ~ 2.45 (0.2 ~ 0.25)
Back direction
Sideways direction
The earth lead wire shall be longer than other lead wires as shown in the
figure for electrical safety in case it slips out of the cord from the anchorage.
Power supply (380/400/415V 3N~)
Circuit breaker
L1
L2
Control cable
L3
N
SG
U1
U2
2
1
Outdoor unit
controller
Insulate the terminal
section with insulation
sleeves.
Firmly secure the power supply
cable, the internal/external
connections and earth wire.
Tie the insulation pipes so that the
power supply cable, control wires,
and earth lead wire do not come into
contact with the compressor and/or
the exposed pipes.
Fig. A (OK)
OUTDOOR UNIT/SINGLE-PHASE MODEL
Power supply (220/230/240V~)
Circuit breaker
Switch
Earth
L
N
SG
U1
Earth
U2
R1
R2
Indoor unit
1-180
Control
terminal block
SG
Cord clamp
Cord clamp
Fig. B (not OK)
Power supply (220/230/240V~)
Switch
Control cable
2
1
Wired remote
controller
Power supply
terminal block
Earth lead wire
Tying band
(Standard
accessories)
Circuit breaker
Switch
L
N
Earth
SG
U1
U2
Outdoor unit