Panasonic S-36PU1E5 Technical Data & Service Manual page 320

R410a inverter, indoor/outdoor units, 4-way cassette, ceiling, wall mounted, low shilhouette ducted, ducted
Table of Contents

Advertisement

• The outdoor unit maintenance remote controller can be used to check the alarm display.
The number of times that LED 1 and 2 blink on the outdoor unit control PCB can be used to check the alarm display.
(Refer to "Checking the LED 1 and 2 Alarm Display on the Outdoor Unit Control PCB.")
Alarm
Code
E01
Remote Controller Reception Error
E02
Remote Controller Transmission Error
E03
Error in Indoor Unit Receiving Signal from Remote Controller (central)
E04
Error in Indoor Unit Receiving Signal from the Outdoor unit
E05
Error in Indoor Unit Transmitting Signal to the Outdoor Unit
E06
Outdoor Unit Failed to Receive Serial Communication Signals from Indoor Unit
E07
Outdoor Unit Sending Failure to Indoor Unit
E08
Duplicate Indoor Unit Address Settings Error
E09
More Than One Remote Controller Set to Main Error
E12
Automatic Address Setting Start is Prohibited while Auto-address Setting in Progress.
E13
Error in Indoor Unit Transmitting Signal to Remote Controller
E14
Main Unit duplication in Simultaneous-operation Multi Control (detected outdoor unit)
E15
Automatic Address Alarm (capacity too low)
4
E16
Automatic Address Alarm (capacity too high)
E18
Faulty Communication in Group Control Wiring
E20
No Indoor Units Connected
F04
Compressor Discharge Temperature Sensor (TD) Trouble
F06
Inlet Temperature Sensor (C1) in Heat Exchanger Trouble
F07
Intermediate Temperature Sensor (C2) in Heat Exchanger Trouble
F08
Outdoor Air Temperature Sensor (TO) Trouble
F12
Compressor Inlet Suction Temperature Sensor (TS) Trouble
F31
Outdoor Unit Nonvolatile Memory (EEPROM) Trouble
H01
Primary (input) Overcurrent Detected
H02
PAM Trouble
H03
Primary Current CT Sensor (current sensor) Failure
H05
Sensor Failure, Compressor Discharge Temperature Sensor (TD) Disconnected
H31
HIC Trouble
L04
Outdoor Unit Address Duplication
L10
Outdoor Unit Capacity not Set
L13
Indoor Unit Type Setting Error
L18
4-way Valve Operation Failure
P03
Compressor Discharge Temperature Trouble
P04
High Pressure Trouble
P05
AC Power Supply Trouble
P13
Alarm Valve Open
P14
O
Sensor Detect
2
P15
Insufficient Gas Level Detected
P16
Compressor Overcurrent Trouble
P22
Outdoor Unit Fan Motor Trouble
P29
Lack of INV Compressor Wiring, INV Compressor Actuation Failure (including locked) due to DCCT Failure
Alarm Meaning
4-24

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents