Sensorless Vector Control; Function Description; Function Setting Method - Hyundai N700E Instruction Manual

Hide thumbs Also See for N700E:
Table of Contents

Advertisement

N700E INSTRUCTION MANUAL

Sensorless Vector Control

5.6

Function description

The N700E inverter has a built-in auto-tuning algorithm.
The N700E inverter can be possible to do high-starting torque and high-precision operation.
The required torque characteristic or speed control characteristic may not be maintained in case
that the inverter capacity is move than twice the capacity of the motor in use .

Function setting method

Select the parameter A31 to 2 (sensorless vector control).
Parameter H03 and H04 select motor capacity and poles (example 4 for 4-poles).
Parameter H02 selects which data(standard data, auto-tuning data) of motor constants you want
the inverter to use.
Note 1. N700E-1600HF/2000HFP ~N7000E-3500HF/3800HFP do not support Sensorless Vector Control