Dc Braking Settings - Hyundai N700E Instruction Manual

Hide thumbs Also See for N700E:
Table of Contents

Advertisement

N700E INSTRUCTION MANUAL
Func-
Name
code
Manual torque boost
A30
frequency setting
V/F
A31
characteristic
curve selection
A32 V/F gain setting

DC Braking Settings

DC braking
A33
function selection
DC braking frequency
A34
setting
DC braking output delay
A35
time setting
A36 DC braking force setting
A37 DC braking time setting
Run-
time
Edit
Sets the frequency of the V/F breakpoint
O
A in graph for torque boost.
Two available V/F curves: three select
codes:
0... Constant torque
1... Reduced torque(reduction of the 1.7
2... Sensorless vector control
X
Sets output voltage gain of the inverter from
20 to 110%
It is proper to set the voltage gain above 100%
in case the rated output voltage is lower than the
rated input voltage
O
Sets two options for DC braking
X
0.... Disable
1.... Enable
The frequency at which DC braking
X
occurs, range is 0.0 to 10.0 Hz in units
of 0.01Hz
The delay from the end of Run command to start of
DC braking (motor free runs until DC braking begins).
Setting range is 0.0 to 5.0sec in units of0.1set.
X
Applied level of DC braking force settable from
X
0 to 50% in units o 0.1%
Sets the duration for DC braking, range is
X
0.0 to 10.0 seconds in units of 0.1sec.
4-9
Description
th
power)
Defaults
100.0%
0
100.0%
0
0.50Hz
0.0sec
10.0%
0.0sec