N700E INSTRUCTION MANUAL

Alarm Terminal Function

5.5

Alarm Terminal [AL1, AL2-AL0]

The alarm output terminals are connected as shown below by default, or after initialization.
The contact logic can be inverted by using the parameter setting C16.
The relay contacts normally contact a.
Convention uses "normal' to mean the inverter has power and is in Run or Stop Mode.
The relay contacts switch to the opposite position when it is Trip Mode or when input power is off.

During normal running or power is turned off

AC250V, 2.5A(Resistor load), 0.2A(Inductive load)
DC30V, 3.0A(Resistor load), 0.7A(Inductive load)

Contact a (Initial setting)

Contact
Power
Run State
ON
Normal
Contact a
ON
(initial
Setting)
OFF
Contact specification
Maximum
When an alarm occurs
AL0-AL1
AL0-AL2
Open
Closed
Trip
Closed
Open
-
Open
Closed
5-21
Minimum
AC100V, 10mA
DC5V, 100mA