Operation Setting And The Frequency Setting From The Digital Operator; Setting Diagram From The Digital Operator - Hyundai N700E Instruction Manual

Hide thumbs Also See for N700E:
Table of Contents

Advertisement

N700E INSTRUCTION MANUAL
3.2.2

Operation setting and the frequency setting from the digital operator

(Remote operator is also same use.)
(Procedure)
(1) Please make sure that connection is right.
(2) Turn the MCCB on to supply power to the inverter.
(The LED "POWER" on the operator should illuminate)
(3) Set the operator with the frequency setting selection.
① Set A01 as indication code, press the (FUNC) key once.
(Code values are shown)
② Set 2(OPE KEYPAD) with (UP/DOWN) key, press the (STR) key once to set the operation setting
for the operator. (Indication code turns back to A01.) [Setting method by OPE-N7 ]
(4) Set the operator with the operation setting selection.
Set A02 as the indication code, press the (FUNC) key once.
Set 2(OPE) with (UP/DOWN) key, press the (STR) key once to set the operation setting for the
operator. (Indication code turns back to A02.)
(5) Set the output frequency
① Set F001 as indication code, by pressing the (FUNC) key once. (Code values are shown.)
② Set to the desired output frequency with the (UP/DOWN) key, press the (STR) key once to store it.
(6) Set Monitor mode
① When monitoring the output frequency, set indication code to d001, and press the (FUNC) key once.
Or when monitoring the operation direction, set indication code to d04, press the (FUNC) key once.
(7) Press the (RUN) key to start operating.
(The "RUN" lamp turns on a light, and the indication changes in response to the monitor mode set.)
(8) Press the (STOP) key to decelerate to a stop.
(When the frequency returns to 0, the RUN lamp light will switch off.).
Fig 3-2 Setting diagram from the digital operator
3-5
N : 30KW(HD)~350KW(HD
)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents