Application - Danfoss ECL Comfort 296 Operating Manual

Application a267
Hide thumbs Also See for ECL Comfort 296:
Table of Contents

Advertisement

Operating Guide ECL Comfort 210 / 296, application A267

5.7 Application

The section "Application" describes specific application related
issues.
Some of the parameter descriptions are universal for different
application keys.
Parameters indicated with an ID no. like "1x607" mean a universal
parameter.
x stands for circuit / parameter group.
MENU > Settings > Application
ECA addr. (ECA address, choice of Remote Control Unit)
Decides the room temperature signal transfer and communication with the
Remote Control Unit.
See Appendix "Parameter ID overview"
OFF:
No Remote Control Unit. Only room temperature sensor,
if any.
A:
Remote Control Unit ECA 30 / 31 with address A.
B:
Remote Control Unit ECA 30 / 31 with address B.
MENU > Settings > Application
Demand offset
The desired flow temperature in heating circuit 1 can be influenced by the
demand for a desired flow temperature from another controller (slave) or
another circuit.
See Appendix "Parameter ID overview"
OFF:
The desired flow temperature in circuit 1 is not
influenced by the demand of any other controller (slave
or circuit 2).
Value: The desired flow temperature is increased by the set
value in 'Demand offset' , if the demand of the slave /
circuit 2 is higher.
VI.GU.G2.02
1x010
The Remote Control Unit must be set accordingly (A or B).
Temp.
1x017
The function of 'Demand offset' can compensate for heat losses
between master and slave controlled systems.
When setting "Demand offset" to a value, the return temperature
limitation will react according to the highest limitation value (Heating
/ DHW).
Setting in
'Demand offset'
Des. flow temp.,
circuit 1
Des. flow temp.,
circuit 2
Time
© Danfoss | 2018.01 | 71