Operating Guide ECL Comfort 210 / 296, application A267
MENU > Common controller > System > M-bus config.
Baud (bits per second)
Circuit
-
300 / 600 / 1200 / 2400
The communication speed between ECL Comfort 296 / 310 / 310B
and the connected energy meter(s).
MENU > Common controller > System > M-bus config.
Command
Circuit
-
NONE / INIT / SCAN / GATEW
The ECL Comfort 296 / 310 / 310B are M-bus masters. In order to verify
connected energy meters, different commands can be activated.
NONE:
No command activated
INIT:
Initialization is activated
SCAN:
Scanning is activated in order to search for connected
energy meters. The ECL Comfort 296 / 310 / 310B
detect the M-bus addresses of up to 5 connected
energy meters and place these automatically in the
"Energy meters" section. The verified address is placed
after "Energy meter 1 (2, 3, 4, 5)"
GATEW: The ECL Comfort 296 / 310 / 310B act as a gateway
between energy meters and ECL Portal. Used only for
service.
MENU > Common controller > System > M-bus config.
M-bus address
Energy meter 1 (2, 3, 4, 5)
Circuit
-
The set or verified address of energy meter 1 (2, 3, 4, 5).
0:
Normally not used
1 - 250:
Valid M-bus addresses
251 - 254: Special functions. Use only M-bus address 254 when
one energy meter is connected.
255:
Not used
100 | © Danfoss | 2018.01
5997
Setting range
Factory setting
300
5998
Setting range
Factory setting
NONE
6000
Setting range
Factory setting
0 - 255
255
Typically, 300 or 2400 baud is used.
If ECL Comfort 296 / 310 / 310B are connected to the ECL Portal, a baud
rate of 2400 is recommendable, provided the energy meter allows this.
Scan time can take up to 12 minutes.
When all energy meters are found, the command can be changed
to INIT or NONE.
VI.GU.G2.02