Operating Guide ECL Comfort 210 / 296, application A267
MENU > Settings > Return limit
Limit (return temp. limitation)
Set the return temperature value you accept for the system.
See Appendix "Parameter ID overview"
When the return temperature falls below or gets higher than the
set value, the controller automatically changes the desired flow /
duct temperature to obtain an acceptable return temperature. The
influence is set in 'Infl. - max.' and 'Infl. - min.' .
MENU > Settings > Return limit
High T out X1 (return temp. limitation, high limit, X-axis)
Set the outdoor temperature value for the low return temperature limitation.
See Appendix "Parameter ID overview"
The corresponding Y coordinate is set in 'Low limit Y1' .
MENU > Settings > Return limit
Low limit Y1 (return temp. limitation, low limit, Y-axis)
Set the return temperature limitation referring to the outdoor temperature
value set in 'High T out X1' .
See Appendix "Parameter ID overview"
The corresponding X coordinate is set in 'High T out X1' .
VI.GU.G2.02
1x030
The return temperature limitation for the DHW circuit is based on the
setting in 'Limit (return temp. limitation)' .
The influence factors are set in heating circuit 1.
If the return temperature limitation value in heating circuit 1 is higher
than the return temperature limitation value in the DHW circuit, the
highest value is used.
1x031
1x032
© Danfoss | 2018.01 | 57