Operating Guide ECL Comfort 210 / 296, application A267
Maximum load ratings:
Relay terminals
Triac (= electronic
relay) terminals
VI.GU.G2.02
4 (2) A / 230 V a.c.
(4 A for ohmic load, 2 A for
inductive load)
0,2 A / 230 V a.c.
Wire cross section: 0.5 - 1.5 mm²
Incorrect connection can damage the electronic outputs.
Max. 2 x 1.5 mm² wires can be inserted into each screw terminal.