Operating Guide ECL Comfort 210 / 296, application A267
MENU > Common controller > System > M-bus config.
Type
Energy meter 1 (2, 3, 4, 5)
Circuit
-
Selecting data range from the M-bus telegram..
0:
Small data set, small units
1:
Small data set, large units
2:
Large data set, small units
3:
Large data set, large units
4:
Volume and energy data only
(example: HydroPort Pulse)
MENU > Common controller > System > M-bus config.
Scan time
Energy meter 1 (2, 3, 4, 5)
Circuit
-
Setting the scanning time for acquiring data of connected energy
meter(s).
MENU > Common controller > System > M-bus config.
ID
Energy meter 1 (2, 3, 4, 5)
Circuit
-
Information about the energy meter's serial no.
MENU > Common controller > System > Energy meters
Energy meter 1 (2, 3, 4, 5)
Circuit
-
Information from actual energy meter about, for example, ID,
temperatures, flow / volume, power / energy.
The shown information depends on the settings made in the "M-bus
config." menu.
VI.GU.G2.02
6001
Setting range
Factory setting
0 - 4
6002
Factory setting
Setting range
1 - 3600 sec
60 sec
Read-out
Setting range
Factory setting
-
Read-out
Setting range
Factory setting
0 - 4
Data examples:
0:
Flow temp., return temp., flow, power, acc. volume, acc. energy.
0
3:
Flow temp., return temp., flow, power, acc. volume, acc. energy,
tariff 1, tariff 2.
See also the "Instructions, ECL Comfort 210 / 310, communication
description" for further details.
See also Appendix for detailed description of "Type".
If the energy meter is battery powered, the scan time should be set to
a high value to prevent a too fast battery draining.
Oppositely, if the flow / power limitation function is used in the ECL
Comfort 310, the scan time should be set to a low value in order to
have quick limitation.
-
0