Assembling
4.3 19" rack mounting
Procedure
Figure 4-1
To mount the device in a 19" rack, follow the steps below:
1. Secure the two mounting brackets with four screws each (M3 x 6 supplied with the
2. Position the device at the required location and screw the device to the 19" rack
32
19" rack mounting of the SCALANCE XR552-12M. SCALANCE XR524-8C/SCALANCE
XR528-6M are mounted in the same way.
product) to the side panels of the device
The maximum tightening torque for these screws is 0.5 Nm.
The dimensions of the mounting brackets depend on the height units of the device.
.
Operating Instructions, 05/2014, A5E03275845-05
.