Technical data
Technical data – General
Designated country (des-
ignation in accordance
with ISO 3166)
Approved unit categories
Type of gas
Gas connection, boiler
side
Flow/return heating con-
nections, boiler side
Flue gas pipe diameter
Supply air pipe diameter
Condensate drain pipe-
work (min.)
Natural gas flow pressure
(G20)
Gas flow rate at 15 °C
and 1013 mbar, (G20)
Min. flue gas mass rate
(G20)
Max. flue gas mass rate
(G20)
Min. flue gas temperature
(at tV/tR = 80/60 °C)
Max. flue gas temperat-
ure (at tV/tR = 80/60 °C)
Unit of type
Nominal rated efficiency
(stationary) at 80/60 °C
Nominal rated efficiency
(stationary) at 60/40 °C
Nominal rated efficiency
(stationary) at 50/30 °C
Nominal efficiency (sta-
tionary) at 40/30 °C
30% efficiency
Standard degree of
utilisation (when set to
nominal heat output, DIN
4702, T8) at 75/60 °C
Standard degree of
utilisation (when set to
nominal heat output, DIN
4702, T8) at 40/30 °C
Remaining delivery pres-
sure (does not apply for
cascade systems)
NOx class
NOx emissions
CO emissions
Nominal CO₂ (G20/G25)
46
VKK GB
VKK GB
806/3-E R1
1206/3-E R1
GB (Great
GB (Great
Britain)
Britain)
I
I
2H
2H
G20 (natural
G20 (natural
gas H)
gas H)
R 1 1/2 inch
R 1 1/2 inch
R 2 inch
R 2 inch
150 mm
150 mm
130 mm
130 mm
21 mm
21 mm
2 kPa
2 kPa
(20 mbar)
(20 mbar)
8.5 m³/h
12.3 m³/h
6.3 g/s
10.0 g/s
35.4 g/s
51.2 g/s
62 ℃
62 ℃
60 ... 70 ℃
60 ... 70 ℃
(140.0
(140.0
... 158.0 ℉)
... 158.0 ℉)
B23; B23P;
B23; B23P;
B53; C33;
B53; C33;
C43; C53;
C43; C53;
C63; C83; C93
C63; C83; C93
97.8 %
97.8 %
100.5 %
100.5 %
103.0 %
103.0 %
105.1 %
105.1 %
108.4 %
108.4 %
106.0 %
106.0 %
110.0 %
110.0 %
100.0 Pa
100.0 Pa
(0.001000 bar)
(0.001000 bar)
5
5
<60 mg/kWh
<60 mg/kWh
<20 mg/kWh
<20 mg/kWh
9.1 ... 9.3 vol.
9.1 ... 9.3 vol.
%
%
Installation and maintenance instructions ecoCRAFT exclusive 0020149561_01
VKK GB
VKK GB
1606/3-E R1
2006/3-E R1
GB (Great
GB (Great
Britain)
Britain)
I
I
2H
2H
G20 (natural
G20 (natural
gas H)
gas H)
R 1 1/2 inch
R 1 1/2 inch
R 2 inch
R 2 inch
150 mm
200 mm
130 mm
130 mm
21 mm
21 mm
2 kPa
2 kPa
(20 mbar)
(20 mbar)
16.9 m³/h
21.2 m³/h
12.2 g/s
19.9 g/s
70.7 g/s
88.4 g/s
62 ℃
62 ℃
60 ... 70 ℃
60 ... 70 ℃
(140.0
(140.0
... 158.0 ℉)
... 158.0 ℉)
B23; B23P;
B23; B23P;
B53; C33;
B53; C33;
C43; C53;
C43; C53;
C63; C83; C93
C63; C83; C93
97.8 %
98.4 %
100.5 %
100.5 %
103.0 %
103.0 %
105.1 %
105.1 %
108.4 %
108.2 %
106.0 %
106.0 %
110.0 %
110.0 %
150.0 Pa
150.0 Pa
(0.001500 bar)
(0.001500 bar)
5
5
<60 mg/kWh
<60 mg/kWh
<20 mg/kWh
<20 mg/kWh
9.1 ... 9.3 vol.
9.1 ... 9.3 vol.
%
%
VKK GB
VKK GB
2406/3-E R1
2806/3-E R1
GB (Great
GB (Great
Britain)
Britain)
I
I
2H
2H
G20 (natural
G20 (natural
gas H)
gas H)
R 1 1/2 inch
R 1 1/2 inch
R 2 inch
R 2 inch
200 mm
200 mm
130 mm
130 mm
21 mm
21 mm
2 kPa
2 kPa
(20 mbar)
(20 mbar)
25.4 m³/h
29.6 m³/h
21.7 g/s
23.5 g/s
106.1 g/s
123.8 g/s
62 ℃
62 ℃
60 ... 70 ℃
60 ... 70 ℃
(140.0
(140.0
... 158.0 ℉)
... 158.0 ℉)
B23; B23P;
B23; B23P;
B53; C33;
B53; C33;
C43; C53;
C43; C53;
C63; C83; C93
C63; C83;
C93
98.4 %
98.4 %
100.5 %
100.5 %
103.0 %
103.0 %
105.1 %
105.1 %
108.2 %
108.2 %
106.0 %
106.0 %
110.0 %
110.0 %
150.0 Pa
150.0 Pa
(0.001500 bar)
(0.001500 bar)
5
5
<60 mg/kWh
<60 mg/kWh
<20 mg/kWh
<20 mg/kWh
9.1 ... 9.3 vol.
9.1 ... 9.3 vol.
%
%