Code Parameter
D.43
Floor-standing boiler temperature
D.44
Digitised ionisation value
D.47
Outside temperature (with weather
compensator)
D.50
Offset for minimum speed
D.51
Offset for maximum speed
D.54
Switch-on hysteresis
D.55
Switch-off hysteresis
D.60
Number of temperature limiter shut-
downs
D.61
Number of ignition device cutoffs
D.63
Number of air-monitoring switch-off
sequences
D.64
Average ignition time
D.65
Maximum ignition time
D.67
Remaining burner anti-cycling time
D.68
Unsuccessful ignitions at 1st attempt
D.69
Unsuccessful ignitions at 2nd at-
tempt
D.71
Maximum target value heating flow
temperature
D.72
External heating pump overrun after
cylinder charging
D.73
Cylinder charging offset, raising the
temperature between the target cyl-
inder temperature and the target flow
temperature when cylinder charging
D.75
Max. charging time for domestic hot
water cylinder without independent
control system
D.76
Floor-standing boiler type
D.77
Limit on cylinder charging output in
kW
D.78
Cylinder charging temperature limit
(target flow temperature in cylinder
charging mode) in °C
0020149561_01 ecoCRAFT exclusive Installation and maintenance instructions
Values or explanations
Display field 0 to 1020
> 700 no flame
< 450 flame detected
< 250 very good flame
Actual value in °C, if the outside temperature sensor is
connected to X41
In rpm/10, adjustment range: -40 to +40
In rpm/10, adjustment range: -40 to +40
0-10 K
0 - 10 K
Number of shutdowns
Number of unsuccessful ignitions in the last attempt
Number of shutdowns
In seconds
In seconds
In minutes
Number of unsuccessful ignitions
Number of unsuccessful ignitions
40 ... 85 ℃
Adjustable from 0 to 600 seconds
0 - 25 K
20 - 90 min
14 = ecoCRAFT
Adjustable cylinder charging output in kW
Maximum value = nominal heat output
55 °C-85 °C
Appendix
Default set-
Own setting
ting
Not
adjustable
Not
adjustable
Not
adjustable
Nominal
value set in
factory
Nominal
value set in
factory
−2
6
Not
adjustable
Not
adjustable
Not
adjustable
Not
adjustable
Not
adjustable
Not
adjustable
Not
adjustable
Not
adjustable
75 ℃
300 s
25 K
45 minutes
Not
adjustable
Automatic
cylinder par-
tial load
80 ℃