1MRS755537
Description
Rated frequency
Time setting range for demand values in
minutes
Non-volatile memory settings
Time setting for disabling new trip targets on the
LCD
Activating the self-supervision
LED test for pickup and trip targets
LED test for programmable LEDs
Trip-circuit supervision
a)
Store counter
Sensor/thermistor selection for input RTD1
Sensor selection for input RTD2
Sensor selection for input RTD3
Sensor/thermistor selection for input RTD4
Motor Protection Relay
Technical Reference Manual - ANSI Version
Parameter
V104
V105
V106
V108
V109
V110
V111
V113
V114
b)
V121
b)
V122
b)
V123
b)
V124
R, W, P
Value
R, W (P)
50 or 60 Hz
R, W
0...999 min
R, W
0...63
R, W (P)
0...999 min
W (P)
1 = Self-supervision output contact is
activated and the READY target LED starts
to flash
0 = Normal operation
W (P)
0 = Pickup and trip LEDs off
1 = Trip LED on, pickup LED off
2 = Pickup LED on, trip LED off
3 = and trip LEDs on
W (P)
0...255
R, W
0 = Not in use
1 = In use
R
0...65535
R, W (P)
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
8 = PTC 0...20 kΩ
R, W (P)
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
R, W (P)
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
R, W (P)
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
8 = PTC 0...20 kΩ
REM 610
REM 610
97