Motor Protection Relay
Technical Reference Manual - ANSI Version
Function
Selection of the latching feature for programmable LED8
When the switch is in position 0 and the signal routed to the
*
LED is reset, the programmable LED will be cleared.
When the switch is in position 1, the programmable LED will
*
remain lit although the signal routed to the LED is reset.
A latched programmable LED can be cleared either via the HMI,
a digital input or the serial bus.
SGB1...SGB5
The DI1 signal is routed to the functions below with the switches of switchgroup
SGB1, the DI2 signal with those of SGB2, and so forth.
Function
0 = targets are not cleared by the digital input signal
*
1 = targets are cleared by the digital input signal
*
0 = targets are not cleared and latched output contacts are not
*
unlatched by the digital input signal
1 = targets are cleared and latched output contacts are
*
unlatched by the digital input signal
0 = targets and memorized values are not cleared and latched
*
output contacts are not unlatched by the digital input signal
1 = targets and memorized values are cleared and latched
*
output contacts are unlatched by the digital input signal
Switching between setting groups 1 and 2 using the digital input
0 = the setting group cannot be changed using the digital input
*
1 = the setting group is changed by using the digital input.
*
When the digital input is energized, setting group 2 will be
activated, if not, setting group 1 will be activated.
When SGB1...5/4 is set to 1, it is important that the
switch has the same setting in both setting
groups.
External tripping by the digital input signal
External triggering of the CBFAIL by the digital input signal
External restart disable by the digital input signal
Activating the emergency start by the digital input signal
Blocking of element (48/14 PICKUP)
the digital input signal (speed switch input)
Blocking of element 50P by the digital input signal
Blocking of element 37 by the digital input signal
Blocking of element 51N by the digital input signal
Blocking of element 46 by the digital input signal
Time synchronization by the digital input signal
2
x (48/14 TDLY) or 48/14 by
REM 610
REM 610
Default setting
0
0
Default setting
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0