ABB REM 610 Technical Reference Manual page 153

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

1MRS755537
Motor Protection Relay
Technical Reference Manual - ANSI Version
Description
Rear communication
protocol
Connection type
Line-idle state
Optional communication
module
Table 8.-4
Parameters for the disturbance recorder
Description
Sampling rate
Station identification/unit
number
Name of the motor drive
Analog channel conversion
factor and unit for I
, I
and
a
b
I
c
Analog channel conversion
factor and unit for the
ground-fault current
Internal trigger signals'
checksum
Internal trigger signal's edge V237
Checksum of internal signal
storing mask
Post-triggering recording
length
External trigger signal's
checksum
External trigger signal's
edge
Checksum of external signal
storing mask
Parameter
Setting range
(channel 0)
V203
0 = SPA
1 = IEC_103
2 = Modbus RTU
3 = Modbus ASCII
V204
0 = loop
1 = star
V205
0 = light off
1 = light on
V206
0 = not in use
1 = in use
Parameter
Setting range
(channel 0)
M15
800/960 Hz
400/480 Hz
50/60 Hz
M18
0...9999
M20
Max 16 characters - ABB -
M80, M81,
Factor 0...65535,
M82
unit (A, kA), e.g. 10,
kA
M83
Factor 0...65535,
unit (A, kA), e.g. 10,
kA
V236
0...8191
0...8191
V238
0...8191
V240
0...100%
V241
0...31
V242
0...31
V243
0...31
REM 610
REM 610
Default
Customer's
setting
setting
0
0
0
0
Default
Customer's
setting
setting
800 Hz
0
00001,CT
00001,CT
2728
0
6842
50 %
0
0
0
153