ABB REM 610 Technical Reference Manual page 48

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

REM 610
REM 610
Table 5.1.4.12.-1
Setting values
Setting
FLA SEC.
t
6x
p
K
c
49 ALARM
49 RESTDIS
T
amb
48/14 PICKUP/FLA
48/14 TDLY
50P/FLA
50P TDLY
51N/ I
CT
n
51N TDLY
37/ FLA
37 TDLY
46 PICKUP/ FLA
46 TDIAL
66
66 COOL/Δt
Trip Fail
RTD1A
RTD1A TDLY
RTD1T
RTD1T TDLY
48
Motor Protection Relay
Technical Reference Manual - ANSI Version
Group selection:
Switching between group 1 and group 2 is accomplished by means of a digital
*
input
Switching between setting groups through group selection has higher
priority than through group configuration.
The setting values can be altered via the HMI or with a PC provided with the Relay
Setting Tool.
Before the relay is connected to a system it must be assured that the relay has been
given the correct settings. If there is any doubt, the setting values should be read
with the relay trip circuits disconnected or tested with current injection; refer to
section Check lists for additional information.
Description
FLA secondary scaling factor 0.50...2.50
Safe stall time
Weighting factor
Time constant dial
Prior alarm level
Restart disable level
Ambient temperature
Start-up current for motor or
pickup value of element 48/14
Start-up time for motor or
operate time of element 48/14
Pickup value of element 50P 0.50...20.0 x FLA
Operate time of element 50P 0.05...30.0 s
Pickup value of element 51N 1.0...100% I
Operate time of element 51N 0.05...300 s
Pickup value of element 37
Operate time of element 37
Pickup value of element 46
Time constant of element 46 at
IDMT characteristic
Restart disable value
Countdown rate of start-up
time counter
Operate time of CBFAIL
Alarm value RTD1A
Operate time RTD1A TDLY
Trip value RTD1T
Operate time RTD1T TDLY
Setting range
a)
b)
2...120 s
20...100%
1...64
50...100%
20...80%
0...70°C
1.00...10.0 x FLA
0.30...80.0 s
CT
n
30...80% FLA
2...600 s
0.10...0.50 x FLA
5...100
5...500 s
2...250 s/h
0.10...60.0 s
0...200°C
1...100 s
0...200°C
1...100 s
1MRS755537
Default setting
1
2 s
50 %
1
95%
40%
40°C
1.00 x FLA
0.30 s
1.00 x FLA
0.05 s
1.0% I
CT
n
0.05 s
50% FLA
2 s
0.20 x FLA
5
5 s
2 s/h
0.10 s
0°C
1 s
0°C
1 s