ABB REM 610 Technical Reference Manual page 57

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

1MRS755537
Switch
Function
SGL1...8/13
DI2 signal
SGL1...8/14
DI3 signal
SGL1...8/15
DI4 signal
SGL1...8/16
DI5 signal
SGL1...8/17
Alarm signal from element 49/38-1
SGL1...8/18
Trip signal from element 49/38-1
SGL1...8/19
Alarm signal from element 49/38-2
SGL1...8/20
Trip signal from element 49/38-2
SGL1...8/21
Trip signal from CBFAIL
SGL1...8/22
Disturbance recorder triggered
ΣSGL1...8
Table 5.1.4.12.-10 New trip target timer
Setting
Description
New trip target
New trip target timer in minutes
No new trip target allowed until the previous one
has been manually cleared
Motor Protection Relay
Technical Reference Manual - ANSI Version
New trip target timer
The new trip target timer can be configured to allow a second trip target on the
LCD. When several protection elements trip, the first trip target will be displayed
until the time, as specified by the NEW TRIP IND. setting value, has expired. After
this, a new trip target can displace the old one. The basic protection functions are not
affected by the NEW TRIP IND. setting.
Non-volatile memory settings
The table below presents data which can be configured to be stored in the non-
volatile memory. All of the functions mentioned below can be selected separately
with switches 1...6 either via the HMI or the SPA bus.
Default setting
SGL1
SGL2
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
4
8
Setting range
0...998
999
REM 610
REM 610
SGL3...8
0
0
0
0
0
0
0
0
0
0
0
Default setting
60
57