ABB REM 610 Technical Reference Manual page 45

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

1MRS755537
Table 5.1.4.11.-1
Resistance values of RTD sensors
Temperature
Platinum TCR 0.00385
°C
Pt 100
-40
84.27
-30
88.22
-20
92.16
-10
96.09
0
100.00
10
103.90
20
107.79
30
111.67
40
115.54
50
119.40
60
123.24
70
127.07
80
130.89
90
134.70
100
138.50
120
146.06
Motor Protection Relay
Technical Reference Manual - ANSI Version
RTD sensor/
thermistor
RTD sensor/
thermistor
Fig. 5.1.4.11.-1
RTD sensor/thermistor connection
RTD temperature vs resistance
Resistance values (Ω) of RTD sensors at specified temperatures are presented in the
table below.
Pt 250
Pt 1000
210.68
842.7
220.55
882.2
230.4
921.6
240.23
960.9
250
1000
259.75
1039
269.48
1077.9
279.18
1116.7
288.85
1155.4
298.5
1194
308.1
1232.4
317.68
1270.7
327.23
1308.9
336.75
1347
346.25
1385
365.15
1460.6
+
-
Common
+
-
Common
Nickel TCR 0.00618
Ni 100
Ni 120
79.1
94.92
84.1
100.92
89.3
107.16
94.6
113.52
100.0
120
105.6
126.72
111.2
133.44
117.1
140.52
123.0
147.6
129.1
154.92
135.5
162.36
141.7
170.04
148.3
177.96
154.9
185.88
161.8
194.16
176.0
211.2
REM 610
REM 610
G
mA
+
-
DIFF
G
mA
+
-
DIFF
Copper TCR
Nickel TCR
0.00427
0.00672
Cu 10
Ni 120 US
7.49
92.76
-
-
8.26
106.15
-
-
9.04
120.00
-
-
9.81
134.52
-
-
10.58
149.79
-
-
11.352
165.90
-
-
12.12
182.84
-
-
12.90
200.64
13.67
219.29
A050429
45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents