Table 5.1.14.1.-5
Mapping of Modbus data: user-defined registers
Description
UDR 1
UDR 2
UDR 3
UDR 4
UDR 5
UDR 6
UDR 7
UDR 8
UDR 9
UDR 10
UDR 11
UDR 12
UDR 13
UDR 14
UDR 15
UDR 16
Table 5.1.14.1.-6
Mapping of Modbus data: status registers
Description
Status register 1
Status register 2
Status register 3
Table 5.1.14.1.-7
Mapping of Modbus data: analog data
Description
Phase current I
x I
(CT)
a
n
Phase current I
x I
(CT)
b
n
Phase current I
x I
(CT)
c
n
Ground-fault current x I
(CT)
n
NPS current
Temperature from RTD1
Temperature from RTD2
Temperature from RTD3
Temperature from RTD4
Temperature from RTD5
Temperature from RTD6
Thermistor 1, resistance value
Thermistor 2, resistance value
82
Motor Protection Relay
Technical Reference Manual - ANSI Version
HR/IR address
DI/Coil bit
(.bit)
1 or 385
2 or 386
3 or 387
4 or 388
5 or 389
6 or 390
7 or 391
8 or 392
9 or 393
10 or 394
11 or 395
12 or 396
13 or 397
14 or 398
15 or 399
16 or 400
HR/IR address
DI/Coil bit
(.bit)
401
402
403
HR/IR address
(.bit)
404
405
406
407
408
409
410
411
412
413
414
415
416
Writeable
address
Writeable
address
DI/Coil bit
Writeable
address
1MRS755537
Value range Comment
Value range Comment
IRF code
See Structure 1
Warning
See Structure 1
codes
See Structure 1
Value range Comment
0...5000
0...50 x FLA
0...5000
0...50 x FLA
0...5000
0...50 x FLA
0...8000
0...800.0% I
(CT)
0...5000
0...50 x FLA
-40...999
°C (signed)
-40...999
°C (signed)
-40...999
°C (signed)
-40...999
°C (signed)
-40...999
°C (signed)
-40...999
°C (signed)
0...200
0...20.0 kΩ
0...200
0...20.0 kΩ
n
a)
a)
a)
a)
a)
a)
b)
b)

Hide quick links: