Maintenance; Ups And Battery Care; Storing The Ups And Batteries; When To Replace Batteries - Eaton Powerware BladeUPS none User Manual

Extended battery module (ebm)
Hide thumbs Also See for Powerware BladeUPS none:
Table of Contents

Advertisement

Chapter 3

UPS and Battery Care

Storing the UPS and Batteries

When to Replace Batteries

EATON Powerware

Maintenance

This section explains how to
S
Care for the UPS and batteries
S
Replace the Extended Battery Modules (EBMs)
S
Recycle used batteries or UPS
For the best preventive maintenance, keep the area around the UPS
clean and dust‐free. If the atmosphere is very dusty, clean the outside of
the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of
25°C (77°F).
NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service
life varies, depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace batteries at
least every 5 years to keep units running at peak efficiency.
If you store the UPS for a long period, recharge the battery every
6 months by connecting the UPS to utility power. The batteries charge
to 80% capacity in less than 5 hours. However, it is recommended that
the batteries charge for 48 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date
has expired and the batteries were never recharged, do not use the
UPS. Contact your service representative.
When the
indicator flashes slowly and the audible alarm beeps
intermittently, the batteries may need replacing. Contact your service
representative to order new batteries.
®
®
BladeUPS
EBM User's Guide
S