Alarm or Condition
Possible Cause
Shutdown imminent.
Shutdown - Low Battery
The UPS is in Bypass mode.
Bypass
Bypass is not available. Input
Bypass
voltage is not within ±12% of
nominal or input frequency is not
within ±3% of nominal.
The batteries may be fully
discharged.
Battery Service
The batteries are not connected
correctly.
Ground wire connection does
Site Wiring Fault
not exist or the line and neutral
(120V models only)
wires are reversed in the wall
outlet.
The UPS internal temperature is
too high. The UPS transfers to
Overtemperature
Bypass mode, allowing the UPS
to cool.
Power requirements exceed
UPS capacity (101–150% for
30 seconds) or the load is
defective.
Overload
Continuous audible
alarm
EATON Powerware
Action
Prepare equipment for shutdown.
The equipment is transferred to utility power; however,
the utility power continues to be passively filtered by the
UPS. Check for one of the following alarms:
Overtemperature, Overload, UPS Failure, or Battery
Service.
The UPS is receiving utility power that may be unstable
or in brownout conditions. The UPS continues to supply
power to your equipment. If conditions worsen, the UPS
may switch to battery power.
Plug the UPS into a power outlet (apply utility power on
hardwired models) for 24 hours to charge the batteries.
After charging the batteries, press and hold the
button for 3 seconds; then check the
If the
Batteries" on page 52.
Check the battery connections. Call your service
representative if the problem persists.
Have a qualified electrician correct the wiring.
To disable this alarm, see "Configuration Mode" on
page 41.
Turn off the UPS. Unplug or remove utility power from
the UPS. Clear vents and remove any heat sources.
Ensure the airflow around the UPS is not restricted. Wait
at least 5 minutes and restart the UPS. If the condition
persists, contact your service representative.
Turn off the UPS. Unplug or remove utility power from
the UPS. Remove some of the equipment from the UPS.
Wait at least 5 seconds until all indicators are off and
restart the UPS.
If the overload condition persists (101–110% for
2 minutes or 111–150% for 30 seconds), the UPS
automatically shuts down.
®
9125 Two-in-One UPS (2500/3000 VA) User's Guide
TROUBLESHOOTING
indicator.
indicator is still flashing, see "Replacing
S
164201374 Rev D
www.powerware.com
65

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerware 9125

Table of Contents