TROUBLESHOOTING
Table 11. Troubleshooting Guide
Alarm or Condition
Possible Cause
μ
The
indicator is not
The power cord is not
on; the UPS does not
;
connected correctly.
start.
The wall outlet is faulty.
The main utility breaker is off.
The remote emergency
power-off (REPO) switch is
active.
The REPO connector is missing.
μ
The
indicator is
The UPS is in Standby mode.
flashing; power is not
available at the UPS
output receptacles.
The UPS operates
The equipment is not connected
normally, but some or all
to the UPS correctly.
of the protected
equipment is not on.
The output receptacle circuit
breaker (if applicable) is open.
One of the load segments has
been turned off through the
power management software.
The UPS does not
The batteries need charging or
provide the expected
service.
backup time.
The UPS is on battery (see
Battery
"Battery Mode" on page 39 for
more information).
Intermittent audible
alarm
Three-minute battery warning.
Warning - Low Battery
64
EATON Powerware
www.powerware.com
Action
Check the power cord connections.
Have a qualified electrician test and repair the outlet.
Verify that the main utility breaker is on.
Reset the REPO switch and restart the UPS.
Verify that the REPO connector is installed on the rear
panel.
Press the On button to supply power to the connected
equipment.
Verify that the equipment is plugged into the UPS
receptacles.
For hardwired models, contact a qualified electrician to
check connections to the power source.
Check the load. Disconnect faulty load equipment. Wait
several minutes before resetting the UPS circuit
breaker.
Reactivate the segment with the software.
Plug the UPS into a power outlet (apply utility power on
hardwired models) for 24 hours to charge the batteries.
After charging the batteries, press and hold the
button for 3 seconds; then check the
If the
Batteries" on page 52.
The UPS is powering the equipment with battery power.
Check the bar graph indicators for available battery
capacity and prepare your equipment for shutdown.
Three minutes or less of battery power remains
(depending on load configuration and battery charge).
Save your work and turn off your equipment.
®
9125 Two-in-One UPS (2500/3000 VA) User's Guide
|
indicator.
indicator is still flashing, see "Replacing
S
164201374 Rev D