How To Replace Extended Battery Modules - Eaton Powerware 9125 Two-in-One UPS 2500 User Manual

Two-in-one ups 2500/300 va
Table of Contents

Advertisement

How to Replace Extended Battery Modules

The Extended Battery Module (EBM) is heavy (see page 61). A minimum of two people are
required to lift the EBM when it is replaced.
To replace the Extended Battery Modules (EBMs):
1.
Unplug the EBM cable from the UPS.
NOTE For 230V models, remove the fixed cover plate, and then unplug the EBM cable from
the UPS.
If additional EBMs are installed, unplug the EBM cable from the
battery connector on each EBM.
2.
If the EBM is in a tower configuration, remove the joining brackets.
3.
If the EBM has pedestals installed, remove the pedestals and
retain.
4.
If the EBM is in a rack, install the mounting handles and brackets on
the new EBM.
5.
Replace the EBM. See "Recycling the Used Battery or UPS" on
page 57 for proper disposal.
6.
Reinstall the pedestals if removed in Step 3.
7.
Reinstall the joining brackets if removed in Step 2.
8.
Plug the EBM cable(s) into the battery connectors as shown in
Figure 45.
For E/EH UPS models, remove the cover from the EBM cable and
plug the EBM cable into the UPS. Attach the fixed cover plate to
the EBM cable.
9.
For additional EBMs, plug the EBM cable into the battery connector
on the adjacent EBM.
For E/EH UPS models, remove the EBM battery connector cover.
Remove the cover from the EBM cable of the second cabinet and
plug the EBM cable into the battery connector on the first EBM.
Attach the fixed cover plate to the EBM cable.
®
EATON Powerware
9125 Two-in-One UPS (2500/3000 VA) User's Guide
UPS MAINTENANCE
C A U T I O N
S
164201374 Rev D
www.powerware.com
55

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerware 9125

Table of Contents