SINGLE-PHASE SERIES 9
Powerware 9125 (700–3000 VA) EBM Backup Times
POWERWARE 9 BATTERY BACKUP TIMES (in minutes)
700-1000 VA Models
Load
Standard
(VA/Watts)
Internal Batteries
200/140
37
400/280
19
700/490
9
850/595
6
1000/700
5
1250-2000 VA Models
Load
Standard
(VA/Watts)
Internal Batteries
400/280
46
700/490
25
850/595
21
1000/700
16
1250/875
11
1500/1050
8
1800/1260
6
2000/1400
5
2500-3000 VA Models
Load
Standard
(VA/Watts)
Internal Batteries
1250/875
16
1500/1050
13
2500/1750
7
3000/2100
5
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
POWERWARE 9 EBC BACKUP TIMES (in minutes)
Discharge Time
EXTERNAL EBC-48 CABINETS. For use with 1250, 1500, 2000 VA
VA
Watts
+1 EBC-48
650
455
838
800
560
662
1000
700
506
1200
840
406
1250
875
387
1400
980
340
1500
1050
315
1600
1120
294
1800
1260
258
2000
1400
224
EXTERNAL EBC-72 CABINETS. For use with 2500, 3000 VA
VA
Watts
+1 EBC-72
1000
700
387
1500
1050
245
2000
1400
175
2500
1750
135
3000
2100
107
1. Actual runtimes not supported by Powerware LanSafe software. *Discharge time @100% of the UPS rating.
Note: Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
+1 EBM
+2 EBMs
271
546
142
278
72
156
59
124
48
104
+1 EBM
+2 EBMs
177
331
96
180
76
142
61
115
46
87
37
70
30
57
26
49
+1 EBM
+2 EBMs
57
90
55
72
28
48
25
38

+2 EBC-48s
+3 EBC-48s
761
705
658
578
501
802
+2 EBC-72s
+3 EBC-72s
368
284
446
225
354
+3 EBMs
+4 EBMs
501
682
272
370
214
292
174
237
131
179
106
144
85
116
74
100
+3 EBMs
+4 EBMs
150
200
120
160
68
88
54
70
+4 EBC-72s
490