M90 & M90L Service Manual

Function explanations for each PCBA

PCB information of Power module
Item
PCBA Name
1
STS Main Board
2
Communication Board
3
SPS Board
4
Interface Board
5
EMI Board
6
Panel Main Board
7
Panel Key Board
8
Panel LED Board
9

Parallel Board

PFC board (Power Factor Correct Board)

The PFC board consists of Rectifier and PFC/Booster.
When UPS works in line mode, the Rectifier and PFC will work, It changes the AC power to DC power stored in
the BUS capacitor. When works in Battery mode, the PFC will only work as boost to get the higher DC power.

INV board (Inverter Board)

The INV Board includes STS and Inverter. It supplies the power for the system, and it converts the
DC power to a pure sine waveform, in the purpose of less or no transfer time, there is one
STS.

CNTL board (Control Board)

The CNTL board is the core of the UPS system. It controls the actions of the semiconductors and other mechani-
cal switches.
COMM board
(Communication Board)
The COMM board is charged of display of the LED/LCD, the communication with the computer, and other impor-
tant tasks

IPOP board

There are charger, input and output EMI on IPOP board. The charger is fully charged the battery capacity. Input
EMI and output EMI are interference prevention at conducted and radiated.

Pre-charger board

The Pre-charger board function is Pre-charging BUS capacity.
Parallel board
The Parallel board is used for parallel communication when the UPS system is running in parallel mode.

Panel Main/LED/key board

The Panel board provides LED and LCD display to the users.
Xtreme Power Conversion Corporation
M90
PCBA serial number
71-301695-xxG
71-300826-xxG
71-301616-xxG
71-300869-xxG
71-301675-xxG
71-301704-xxG
71-300846-xxG
71-300528-xxG
71-300821-xxG
Uninterruptible Power Supply
Quantity
Remark
1
1
2
1
1
1
1
1
1
Page 11

Advertisement

Table of Contents
loading

This manual is also suitable for:

M90l

Table of Contents