Instruction manual - GB
Instruction
manual
www.atmos.cz

Advertisement

Table of Contents
loading

Summary of Contents for Atmos DC 15

  • Page 1 Instruction manual - GB Instruction manual www.atmos.cz...
  • Page 2 Instruction manual - GB www.atmos.cz...
  • Page 3: Table Of Contents

    23. Laddomat 22 24. Thermoregulatory valve 25. Operating a system with accumulation tanks The standard ATMOS accumulation tanks provided Tank insulation Advantages 26. Connection of overheat protecting cooling loop with a safety valve Honeywell TS 131 - 3/4 ZA or WATTS STS20 28 27.
  • Page 4 In non-compliance with these instructions the drum’s and the heatproof pipes’ service life may dramatically decrease. The boiler drum may cor- rode in as little time as 2 years. CAUTION - INSTALLER SHOULD ALWAYS COMPLY WITH LOCAL PLANNING AND BUILDING REQUIREMENTS. www.atmos.cz 4-GB...
  • Page 5: Intended Use

    Instruction manual - GB 1. Intended use The environmentally friendly boilers ATMOS DC 15/18/20/22/25/30/32/40/50/70/75 are designed for heating family houses, cottages, holiday houses and other similar buildings. Boilers are suitable for buildings with heat loss ranging between 15 - 75 kW, depending on type. The boilers are construct- ed mainly for burning logs.
  • Page 6: Control Panel For Boilers With Ventilator

    1. Thermometer 6. Ignition valve pulling rod 2. Main switch 7. Area for electronic regulation of the heating 3. Waste gas thermostat system (92x138 mm) 4. Control thermostat (boiler) 8. Pump thermostat (only DC15E) 5. Safety irreversible thermostat www.atmos.cz 6-GB...
  • Page 7: Advantages Of Boilers

    (DC70S, DC15E excluded). Large fuel hopper allows burning of the log pieces with the maximum length 330 - 1.000 mm, depending on the boiler type. Large pieces of waste wood can also be burned. All boilers are equipped with cooling loop for overheating protection. www.atmos.cz GB-7...
  • Page 8: Technical Data

    Instruction manual - GB 3. Technical data www.atmos.cz 8-GB...
  • Page 9: Boiler Drawings Key

    150/ 150/ 1008 1008 1008 1008 1008 1152 1106 1106 1106 1230 6/4” 6/4” 6/4” 6/4” 6/4” 6/4” 6/4” 6/4” 6/4” 2” 2” 2” 2” 2” 2” * boiler width is 555 mm after disassembling the side hoods www.atmos.cz GB-9...
  • Page 10: Drawings Of Boilers

    Instruction manual - GB Drawings of boilers www.atmos.cz 10-GB...
  • Page 11 Cut away view - DC15E Cut away view – DC70S Combustion chamber 3. Ash-pan door 5. Heatproof shaped piece - nozzle 31. Heatproof shaped piece – half moon 32. Heatproof shaped piece – combus- tion area plate. 34. Cleaning aperture www.atmos.cz GB-11...
  • Page 12: Extraction Ventilator Schematics

    700 mm. Roof of the lower combustion area must always be fully pressed against the boiler rear wall. 2. For type DC75SE Roof for this boiler type consist of two pieces – see figure (DC75SE – 2 x 500mm) www.atmos.cz 12-GB...
  • Page 13: Boiler Accessories

    5. Boiler accessories Steel brush with accessories 1 pc Poker 1 pc Filling-in valve 1 pc Operating and maintenance instructions manual 1 pc Draught regulator - HONEYWELL FR 124 (DC50SE excluded) 1 pc Ashtray (only for DCxxGS, DC15E) 1 pc www.atmos.cz GB-13...
  • Page 14: Fuel

    • Example – spruce wood which has been stored for 1 year under shelter – see graph The boilers maximum output with wet fuel illustrated in the graph DC 15 E DC 18 S - 13 DC 22 S - 14...
  • Page 15: Boiler Bases

    The chimney draught is directly dependent on its cross section, height and the inner wall ruggedness. It is not permitted to connect another appliance into a chimney into which a boiler is connected. The chimney diameter must not be smaller than the boiler outlet www.atmos.cz GB-15...
  • Page 16: Flue-Gas Duct

    ČSN 061008. These are appropriate for mobile installations, wooden cottages etc. 1 - Waste gas thermometer 2 - Cleaning aperture 3 - Throttle valve (draught limiter) INFO - In case of excessive chimney draught, install a throttle valve or draught limiter (regulator) /3/. www.atmos.cz 16-GB...
  • Page 17: Fire Prevention During Installation And Use Of Heating Appliances

    PVC etc.) the boilers must be put out of operation long enough before the risk occurrence. No items from flammable materials may be placed on the boilers or near them for a distance lower than the specified safe distance (more see ČSN EN 13501-1). www.atmos.cz GB-17...
  • Page 18: Connecting Boilers To The Electrical Power Network

    Connectors in side hoods of the boiler: Connector in the right side hood Connector in the left side hood 1 - connector for income cabel (L - brown, N - blue, PE - green/yellow) 2 - connector for extraction fan www.atmos.cz 18-GB...
  • Page 19: Wiring Diagram Of Electromechanical Regulation With Extraction Ventilator, Type Ucj 4C52 (Dc18S - Dc50S)

    PŘEHODIT SVORKY "ST2" ZA "ST2 REG" PŘI OVLÁDÁNÍ KOTLOVÉHO VENTILÁTORU/ČERPADLA ELEKTRONICKOU REGULACÍ WHEN ELECTRONIC REGULATION CONTROL BOILERPUMP  CONNECTORS "TČ95" MUST BE UNCONNECT DEN KONNEKTOREN "TČ95" ABKLEMMEN BEI DER KESSELPUMPE BEDIENUNG DER ELEKTRONISCHE REGELUNG KONEKTORY "TČ95" ODPOJIT PŘI OVLÁDÁNÍ KOTLOVÉHO ČERPADLA ELEKTRONICKOU REGULACÍ www.atmos.cz GB-19...
  • Page 20: Wiring Diagram For Dc75Se - Electromechanical Regulation With An Ucj 4C52 Type Extraction Ventilator, Valid From 12/2007

    KONEKTORY "STC" A "ST2" ODPOJIT PŘI OVLÁDÁNÍ KOTLOVÉHO ČERPADLA A VENTILÁTORU ELEKTRONICKOU REGULACÍ WHEN ELECTRONIC REGULATION CONTROL BOILER PUMP  CONNECTORS "TČ70" AND "TČ95" MUST BE UNCONNECT DEN KONNEKTOREN "TČ70" UND "TČ95" ABKLEMMEN BEI DER KESSELPUMPEBEDIENUNG DER ELEKTRONISCHE REGELUNG KONEKTORY "TČ70" A "TČ95" ODPOJIT PŘI OVLÁDÁNÍ KOTLOVÉHO ČERPADLA ELEKTRONICKOU REGULACÍ www.atmos.cz 20-GB...
  • Page 21: Wiring Diagram Of Electromechanical Regulation Of The Dc15E Type Boiler, Valid From 12/2007

    ČSN EN ISO 12100:2012, ČSN EN 953+A1:2009, ČSN EN ISO 11202:2011, ČSN EN ISO 3746:2011, ČSN ISO 1819:1993, ČSN EN 60335-1ed.2:2003 CAUTION – the boiler must be installed in compliance with a design prepared in ad- vance. Installation may only be carried out by persons trained by the manufacturer. www.atmos.cz GB-21...
  • Page 22: Choice And Connection Method Of Control And Heating Elements

    For the heating system regulation we recommend regulation elements provided by the following companies: a) ATMOS ACD 01 - Eqvithermal controller set for solid fuel boilers b) KOMEXTHERM, Praha tel.: +420 235 313 284 c) KTR, Uherský Brod tel.: +420 572 633 985...
  • Page 23: Boiler Corrosion Protection

    For outputs of 15 - 100 kW it is also possible to keep the minimum temperature of the return- ing water (65 - 75 °C) by utilising a three-way mixing valve with an electric actuator and electronic regulation. 19. Specified boiler connection with Laddomat 22 www.atmos.cz GB-23...
  • Page 24: Specified Boiler Connection With Thermoregulation

    Instruction manual - GB 20. Specified boiler connection with thermoregulation ATTENTION – when connecting the cooling loop to prevent overheating, it is possible to omit the return valve on the thermo-valve and pump by pass. 21. Boiler connection with equilizing tank www.atmos.cz 24-GB...
  • Page 25: Recommended Wiring Diagram With Laddomat 22 And Accumulators

    Instruction manual - GB 22. Recommended wiring diagram with Laddomat 22 and ac- cumulators www.atmos.cz GB-25...
  • Page 26: Thermoregulatory Valve

    Recommended sizes of the thermoregulatory valve TV 60 °C (65/70/75 °C). For boilers: D15E, DC18S, DC20GS, DC22S, DC22SX DC25S, DC25GS, DC30SX ..DN 25 DC32S, DC32GS, DC40GS, DC40SE, DC40SX ........DN 32 DC50S, DC50SE, DC70S, DC75SE ..........DN 40, DN 50 www.atmos.cz 26-GB...
  • Page 27: Operating A System With Accumulation Tanks

    Output Volume 1000 - 1500 1500 - 2000 1500 - 2000 2000 - 2500 2500 - 3000 3000 - 4000 4000 - 5000 5000 - 6000 The standard ATMOS accumulation tanks provided TANK TYPE VOLUME ( l ) DIAMETER (mm)
  • Page 28: Connection Of Overheat Protecting Cooling Loop With A Safety Valve Honeywell Ts 131 - 3/4 Za Or Watts Sts20

    2 – 4 cm gap between the recess and fuel is created; which allows the waste gas passage. Place paper or wood wool on top of the kindling, www.atmos.cz 28-GB...
  • Page 29: Waste Gas Thermnostat Setting

    (80 - 90 °C) (DC50SE excluded). The output (draught) regulator adjustment should be done carefully because it not only regulates the output; but also protects the boiler against overheating. The setting should be in compliance with the enclosed ‚Assembly and Setting Instructions‘ www.atmos.cz GB-29...
  • Page 30: Draught Regulator - Honeywell Braukmann Fr 124 - Assembly Instructions

    95 °C, the control flap valve must be fully closed (only providing the setscrew gap). It is always necessary to fine-tune the specified op- erating temperature (80 - 90 °C) utilising the mixing valves behind the boiler either manually or by electronic regulation with electric actuator. www.atmos.cz 30-GB...
  • Page 31: Boiler Output And Combustion Setting

    (up to the stop + 1 turn anticlockwise). Without ventilator – DC15E Basic setting of primary-secondary air ratio Optimum setting: fully closed (5 mm) + 5÷10 mm Maximum setting: fully closed (5 mm) + 10÷20 mm www.atmos.cz GB-31...
  • Page 32: Boiler With Compressive Ventilator Dc70S

    CAUTION – during operation, the ignition valve pulling rod must be retracted, other- wise damage to the ventilator (S) will occur. Otherwise, the ventilator (S) will sustain damage. www.atmos.cz 32-GB...
  • Page 33: Steady Heat Operation

    Area underneath these sheets must be cleaned regularly once per 7 to 14 days. Boilers DC70S must be checked at least 2x a year and the compressive ventilator and the air duct may need cleaning. If necessary, clean the area behind the heating area rear screen from tars and ash /41/, /19/. www.atmos.cz GB-33...
  • Page 34 Sample cleaning of the flue way with a wire Sample cleaning of the flue way - bottom lid brush - upper lid Sample cleaning of impeller and checking Checking and cleaning regulation of primary- uprightness of vane on extract ventilator secondary air ratio via cleaning lid www.atmos.cz 34-GB...
  • Page 35: Ceramic Ash Areas

    Maximum ash quantity ! NOTE –regular and thorough cleaning is important for permanent stabilised output and a long service life of your boiler. If not cleaned properly, damage to the boiler may occur –the manufacturer’s guarantee is rendered invalid www.atmos.cz GB-35...
  • Page 36: Heating System Maintenance - Including Boilers

    Cleaning doors must always be properly closed. CAUTION - Follow valid fire regulations and have in reach portable fire extinguisher. If any non-standard behavior of the boiler shut down the boiler from operation and call the service. www.atmos.cz 36-GB...
  • Page 37: Possible Failures And Troubleshooting

    - clean the ventilator including the ducting from tar and sedi- ments Ventilator does not turn - defective capacitor - replace - defective motor - replace - bad contact in plug of motor - check - measure cable lead www.atmos.cz GB-37...
  • Page 38: Spares

    - if present – is positioned backwards). The secondary air is brought to the nozzle from the rear section of the boiler. Place the nozzle on its holder and fully push towards the rear of boiler. www.atmos.cz 38-GB...
  • Page 39: Door Sealing Cord Replacement

    36. Environmental protection The ATMOS gasifying boilers comply with the most demanding environmental requirements and were awarded the “Environmentally friendly product” mark, in compliance with directive No. 13/2002 of the Ministry of Environment of the Czech Republic. The boilers are certified in compli- ance with the European standard EN 303-5 and they fall within class 3, 4 and 5.
  • Page 40: Guarantee Conditions

    - company representing ATMOS in the particular country for the particular region - installation company that carried out the installation - Jaroslav Cankař a syn ATMOS, Velenského 487, 294 21 Bělá pod Bezdězem, Czech Republic, Telephone. +420 326 701 404 www.atmos.cz...
  • Page 41: Boiler Installation Report

    Boiler functions and all regulations and safety Size: ............elements were inspected during the operation Moisture content: .........* start-up. Person responsible for the inspection: ..........Date: ......Stamp: ..........Customer’s signature: ........(Responsible person’s signature) * measured values www.atmos.cz GB-41...
  • Page 42: Annual Inspections Records

    Date Date Date Date stamp and signature stamp and signature stamp and signature stamp and signature Date Date Date Date stamp and signature stamp and signature stamp and signature stamp and signature www.atmos.cz 42-GB...
  • Page 43: Records Of Guarantee Period And Post-Guarantee Period Repairs

    Repair: ..............................Repair: ..............................Repair: ..............................Repair: ..............................Repair: ..............................Repair: ........................................repair carried out by, date Repair: ..............................Repair: ..............................Repair: ..............................Repair: ..............................Repair: ..............................Repair: ..............................Repair: ........................................repair carried out by, date www.atmos.cz GB-43...
  • Page 44 Instruction manual - GB www.atmos.cz 44-GB...